6. Configure the Min Speed Stop Delay time.
The Default is 60 Seconds. The range is 0- 3600 seconds.
7. Configure the Hysteresis Value
Hysteresis is the monitored difference (window) between the warning and alarm values, and the actual values used to
deactivate a Condition event. It prevents a condition from continuously activating and deactivating when the monitored
value fluctuates above and below the High or Low limits.
The default is .20 of the units selected for the source. The range is .20 to 9999.00.
You may have to change the configuration of Parameter 80.19 to allow Monitoring of the values when the PumpSmart
PS220 is either Running or Always. The default is ALWAYS.
This change will need to be done manually by accessing that specific parameter directly:
From the HOME SCREEN follow the path: Menu>Parameters>Complete List>Arrow Down to GROUP 80>80.19>
Edit>Save
The Parameters used in configuring the condition monitoring function are listed in the table below.
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...