PS220 Configuration & Operation Guide
261 PS220
Parameter
Listing
PS220 Parameter Listing
GROUP 1 ACTUAL VALUES
DESCRIPTION
Scaling
1.01
MOTOR SPEED
Measured or estimated motor speed -30000 – 30000 RPM
See parameter
46.01
1.02
MOTOR SPEED ESTIMATED
Estimated motor speed in rpm. -30000 – 30000 RPM
1.03
MOTOR SPEED %
Motor speed displayed as a percent of the synchronous speed. (-1000-1000.00%)
10=1%
1.04
ENCODER 1 SPEED FILTER
Speed of encoder 1 in rpm. -30000 – 30000RPM
-
1.05
ENCODER 2 SPEED
Speed of encoder 1 in rpm. -30000 – 30000RPM
-
1.06
OUTPUT FREQUENCY
Estimated drive output frequency in Hz. -600-600 Hz
See parameter
46.02
1.07
MOTOR CURRENT
Measured (absolute) motor current in A. 0-30000
See parameter
46.05
1.08
MOTOR CURRENT % OF MOTOR NOM
Shows the value of 01.07 Motor Current used in percent. 0-1000%
1=1%
1.10
MOTOR TORQUE
Motor torque in percent of the nominal motor torque. -1600-1600 %)
See parameter
46.03
1.11
DC VOLTAGE
Measured DC Bus link voltage. 0.00-2000.00V
10=1
1.13
OUTPUT VOLTAGE
Calculated motor voltage in VAC. 0-2000V
1=1V
1.14
OUTPUT POWER
Drive output power. The unit is selected by parameter 96.16 Unit selection. -32767-32767
See parameter
46.04
1.15
OUTPUT POWER % OF MOTOR NOM
Shows the value of 01.14 Output power in percent of the nominal power of the
motor. -300 - 300.00%
10=1%
1.17
MOTOR SHAFT POWER
Estimated mechanical power at motor shaft. The unit is selected by parameter 96.16 Unit
Selection. -327680-32767.00
1=1 unit
1.18
INVERTER GWh MOTORING
Amount of energy that has passed through the drive (towards the motor) in full
giga- watt-hours. The minimum value is zero. 0-32767 GWh
1=1 GWh
1.19
INVERTER MWh MOTORING
Amount of energy that has passed through the drive (towards the motor) in full mega-
watt-hours. Whenever the counter rolls over, 01.18 Inverter GWh motoring is
incremented. The minimum value is zero. 0-1000 MWh
1=1 MWh
1.20
INVERTER kWh MOTORING
Amount of energy that has passed through the drive (towards the motor) in full kilo-
watt-hours. Whenever the counter rolls over, 01.19 Inverter MWh motoring is
incremented. The minimum value is zero. 0-1000kWh
10=1 kWh
1.21
U-PHASE CURRENT
Measured U-phase current. -3000-3000 A
See
parameter
46.05
1.22
V-PHASE CURRENT
Measured V-phase current. -3000-3000 A
1.23
W-PHASE CURRENT
Measured W-phase current. -3000-3000 A
1.24
FLUX ACTUAL %
Used flux reference in percent of nominal flux of motor. 0-200%
1=1%
1.25
INU MOMENTARY cos
Momentary cosphi of the drive. -1.00 – 1.00
100=1
1.29
SPEED CHANGE RATE
Rate of actual speed change. Positive values indicate acceleration, negative values
indicate deceleration. See also parameters 31.32 Emergency ramp supervision, 31.33
Emergency ramp supervision delay, 31.37 Ramp stop supervision and 31.38 Ramp stop
supervision delay. -15000-15000 rpm/s
1=1 rpm/s
1.30
NORMAL TORQUE SCALE
Torque that corresponds to 100% of nominal motor torque. The unit is selected by
parameter 96.16 Unit selection. Note: This value is copied from parameter 99.12 Motor
nominal torque if entered. Otherwise the value is calculated from other motor data. 0.00 –
xxx Nm
or lb ft.
1=1 unit
1.31
AMBIENT TEMPERATURE
Measured temperature of incoming cooling air. The unit is selected by parameter 96.16 Unit
Selection. -40 -200.0 °F
1=1
1.32
INVERTER GWh REGENERATING
Amount of energy that has passed through the drive (towards the supply) in full
giga- watt-hours. The minimum value is zero. 0-32767
1=1 GWh
1.33
INVERTER MWh REGENERATING
Amount of energy that has passed through the drive (toward the supply) in full mega-
watt-hours. Whenever the counter rolls over, 01.32 Inverter GWh regenerating is
increment- ed. The minimum value is zero. 0-1000 MWh
1=1 MWh
1.34
INVERTER kWh REGENERATING
Amount of energy that has passed through the drive (towards the supply) in full kilo-
watt-hours. Whenever the counter rolls over, 01.33 Inverter MWh regenerating is
increment- ed. The minimum value is zero. 0-1000 kWh
1=1 kWh
1.35
MOT-REGEN ENERGY GWh
Amount of net energy (motoring energy – regenerating energy) that has passed through
the drive in full gigawatt hours. -32768 – 32767 GWh
1=1 GWh
1.36
MOT-REGEN ENERGY MWh
Amount of net energy (motoring energy – regenerating energy) that has passed through
the drive in full megawatt hours. Whenever the counter rolls over, 01.35 Mot – regen
energy GWh is incremented or decremented.(-1000-1000 MWh
1=1 MWh
1.37
MOT-REGEN ENERGY kWh
Amount of energy (motoring energy - regenerating energy) that has passed through the
drive in full kilowatt-hours. Whenever the counter rolls over, 01.36 Mot - regen energy MWh
is incremented or decremented. (-999-999 kWh)
1=1 kWh
1.61
ABS MOTOR SPEED USED
Absolute value of 01.01 Motor speed used. 0.00-30000.00 rpm
See parameter
46.01
1.62
ABS MOTOR SPEED %
Absolute value of 01.03 Motor speed %. 0.00-1000.00%
10=1%
1.63
ABS OUTPUT FREQENCY
Absolute value of 01.06 Output frequency. 0.00-600.00 Hz
See parameter
46.02
1.64
ABS MOTOR TORQUE
Absolute value of 01.10 Motor torque. 0.0-1600.0%
See parameter
46.03
1.65
ABS OUTPUT POWER
Absolute value of 01.14 Output power. 0.00-32767.00
1=1 unit
1.66
ABS OUTPUT POWER % MOTOR NOM
Absolute value of 01.15 Output power % of motor nom. 0.00-300.00%
10=1%
1.68
ABS MOTOR SHAFT POWER
Absolute value of 01.17 Motor shaft power. (0.00-32767.00
1=1 unit
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...