PS220 Configuration & Operation Guide
PS220 258
Fault T
racing
CODE
(HEX)
WARNING
CAUSE
WHAT TO DO
5093
Rating ID mismatch
The hardware of the drive
does not match the
information stored in the
memory unit. This may occur
after a firmware update or
memory unit replacement.
•
Cycle the power to the drive.
•
Cycle the control board in Parameter 96.01 (change to
1)
5681
PU communication
The way the control units 24vDC
is connected does not
correspond to parameter
setting.
•
Check setting of 95.04 Control board supply.
Communication errors
detected between the drive
control unit and the power
unit.
•
Check the connection between the control unit and
the power unit.
64A5 Licensing fault
Running the control program
is prevented either because
a restrictive license exists, or
because a required license is
missing.
•
Record the auxiliary codes of all active licensing
faults and contact your ITT representative for further
instructions.
64B0
Memory unit detached
The memory unit was detached
when the control unit was
powered.
•
Switch off the power to the control unit and reinstall
the memory unit.
•
In case the memory unit was not actually removed
when the fault occurred, check that the memory unit
is properly inserted into its connector and its mounting
screw is tight. Reboot the control unit (using parameter
96.08 Control board boot) or by cycling power. If the
problem persists, contact your local ITT representative.
6581
Parameter system
Parameter load or save failed. •
Try forcing a save using parameter 96.07 Parameter
save manually. Retry.
65A1 FBA A parameter conflict
The drive does not have a
functionality requested by PLC,
or requested functionality has
not been activated.
•
Check PLC programming.
•
Check settings of parameter groups 50 Fieldbus
adapter (FBA) and 51 FBA A settings.
7080
Option module Comm loss Communication between drive
and an option module is lost.
•
Check that all option modules are properly seated
in their slots.
•
Check that all option modules or slot connectors are
not damaged. To pinpoint the problem, try installing the
modules into different slots one at a time.
7081
Control panel loss
Programmable fault: 49.05
Communication loss action
Control panel (or PC tool) has
stopped communicating.
•
Check PC tool or control panel connection.
•
Check control panel connector. Disconnect
and reconnect the control panel.
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...