PS220 Configuration & Operation Guide
189 PS220
Function & F
eatures
Relay Outputs
The PumpSmart PS220 has 3 Form C “Dry Contact” relays on board as standard. They are fully assignable to oper-
ating and fault conditions. Relays will revert to original states once warnings, faults and the operating conditions
are reset or cleared. Each can be forced on, off, and inverted. By default, Relay 1 is configured for Ready, Relay 2 is
configured for Running, and Relay 3 is configured for Fault. If they are not used, they will show “Force Off” in their
configuration status. Additional relays can be added with an extension module.
The relay outputs should be configured using the PS220 Configuration Wizard. To get to the wizard from the home
view follow the path:
Menu>PS220 Configuration>I/O Configuration>No>Relays>
Relay Output Technical Information.
Switching Capacity is 30 VDC/250VAC with max of 2 Amps.
Refer to the PS220 Wiring Diagram for detailed information on connections required.
Parameter
Name
Value/Range
Notes
76.06
RELAY R01 SOURCE
24 Individual Choices
Default for RO1 (default READY)
76.07
RELAY R02 SOURCE
Default for RO2 (default RUNNING)
76.08
RELAY R03 SOURCE
Default for RO3 (default FAULT)
FORCE OFF
Force the relay to the off state
FORCE ON
Force the relay to the on state
INVERTED FAULT
A general VFD or PUMP related fault has occurred. Normally Open
FAULT
A general VFD or PUMP related fault has occurred.
RUNNING
VFD is running the motor. Will remain on until stop at end of
deceleration
ramp.
FLOW BYP SMRT FLW
Minimum flow bypass valve control
triggers the relay to open the valve when using SmartFlow
PIPE CLEAN
A pipe cleaning sequence is being executed. The relay remains
energized until
the completion of the cleaning sequence.
COND1 HI ALARM
Condition 1 HI Alarm is active
COND2 HI ALARM
Condition 2 HI Alarm is active
FLOW BYP EXT FLW
Minimum flow bypass valve control
triggers the relay to open the valve when using an external flow meter.
PUMP FLTS/WRNGS
A general pump related warning or fault has occurred
READY
Drive is ready to run (no faults or warnings)
SECOND PROTECT A
Secondary Protect A activation
SECOND PROTECT B
Secondary Protect B activation
PCS REQ
A pump cleaning sequence has been requested. The relay remains
energized
until the completion of the cleaning sequence.
PCS EXE
A pump cleaning sequence is being executed.
The relay remains energized
until the completion of the cleaning sequence.
PUMP PROTECT
Pump protection activation
MULTI VAR ACTIVE
Multivariable control is active
SPEED OVERIDE
Speed override is active
COND1 LOW ALARM
Condition 1 LOW Alarm is active
COND2 LOW ALARM
Condition 2 LOW Alarm is active
START DELAY ACTIVE
Drive is under a start delay (74.04
REMOTE
Remote/Local in in Remote mode
OTHER
Selecting other will allow relay to change state based on a specific
Parameter or setting.
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...