PS220 Configuration & Operation Guide
PS220 240
Functions &
Features
Pipe Cleaning Function
The PS220’s Pipe Cleaning function will allow for a high flow flushing of the discharge piping system. This
will reduce sedimentation that may have accumulated in the piping and he overall wear on the piping
system over time. The PS220 can be configured to execute the pipe clean sequence on every start, or strictly
based on actual accumulated pump/motor running hours. The pump will be run at full speed when this
function is executed.
When the Pipe Cleaning function is initiated, all PS220 functional control is disabled. It is automatically
enabled once the function completes.
When the Pipe Cleaning function is active the message “Pipe Clean Running” will be displayed on the Key-
pad and will be captured and stored in the event log.
This functionality can be configured with the PumpSmart PS220 Configuration Wizard. To access this Wiz-
ard from the Home View, follow the path: Menu>PS220 Configuration>Water Function>Pipe Clean>l
The individual steps that will be performed are:
1. Configure the method to enable Pipe Cleaning function.
2. Configure the Pipe Clean Time interval,
3. Configure the Pipe Clean Cycle Time.
4. Exit the Wizard
1. Configure the method to enable the Pipe Cleaning function.
The two selection choices are
1. At every Start command
2. Based on run time interval.
2. Configure the Pipe Clean Time interval.
This is the time interval used for step 1B. The default is 100 Hours.
3. Configure the Pipe Clean Cycle Time.
This is the total time that the Cleaning Cycle will run. The default is 600 Seconds (10 Minutes).
4. Exit the Wizard
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...