PS220 Configuration & Operation Guide
77 PS220
Pump & VFD Protection
1. “ARROW RIGHT” To change
2. “ARROW UP/DOWN” to change
3. “Save“
4. “ARROW DOWN”
5. Configure the Config Speed Min setting.
The PumpSmart PS220 can be configured to run to a “Config Speed Min” speed choice when “Alarm
and Control” has been configured as the Response for the Pump Protection selection. The choices are:
1. The Minimum Speed set in Parameter 30.11. (SPD=MIN)
2. ZERO (0) RPM or to stop. (Speed =0)
Notes:
1. This choice cannot be selected for individual Responses. This is applied “globally” when selected.
2. This selection should not be used if “Min-Speed” is selected for the PID sleep function in process
control. The sleep function will need to be changed to “INTELL SLEEP”
6. Configure the Stop Delay Min Speed.
1. “ARROW RIGHT” To change
2. “ARROWS” to change
3. “Save”
4. “ARROW DOWN”
7. Exit the Wizard
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...