PS220 Configuration & Operation Guide
PS220 214
Functions &
Features
5. Configure the Transmitter(s) and the associated Analog Inputs to be used for
the TDH calculations.
A. For the Discharge Transmitter
1. Select the Analog Input that will be used.
2. Configure the Analog Input for use as Discharge pressure.
If you have already configured a discharge transmitter with the Process Control Wizard, please select “PROC TTANS 1” and
skip to step B below. You will not have to reconfigure the use of this transmitter.
3. Configure the Minimum and Maximum scaled values.
4. Configure the Unit of measure for the transmitter
B. For the Suction Transmitter
1. Select the Analog Input that will be used.
2. Configure the Analog Input for use
3. Configure the transmitter will read in Gauge or Absolute pressure.
Gauge pressure does not correct for the local Barometric pressure.
4. Configure the Minimum and Maximum scaled values
NOTE:
An unused Analog Input (AI) will need to be used for either of these 2 choices in step 5 to function correctly. Please check
the settings of the Analog Inputs currently in use by going to: Menu>PARAMATERS> Complete List>Scroll down to
Group 76>Select and View 76.01&02. If available “NOT SELECTED” will be displayed. You may have to add an Extension
Card to use additional inputs.
6. Configure Fluid Specific Gravity (Same as Basic)
Please refer to Specific Gravity section in this manual for the detailed information required to complete this step.
7. Execute a Smart flow Tune (Same as Basic)
Please refer to the Smartflow Tune section in this manual for detailed information on how to execute this step.
8. Exit the Wizard
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...