PS220 Configuration & Operation Guide
151 PS220
Function & F
eatures
Flow Totalizer
The PS220’s Totalizer function can be used in a “Batch Operation” when a defined total flow volume is required to be
pumped. When the Batch is completed the PS220 with stop the pump. Prior to a new start command, the value from
the previous total must be reset. This can be done manually via parameter 84.02, or with a Digital Input configured for
“TOTALIZER RESET”.
Notes
1. The Flow Totalizer function will not operate in Multi-Pump mode.
2. A Flow source is required to be configured to utilize the totalizer function.
3. The total pumped volume will update every 5 seconds and only will display whole numbers.
The table below lists all of the Parameters used in this function:
Parameter
Name
Value/Range
Note(s)
84.01
TOTL SYS VOL STPT 0.0 – 999999.0
The Default is 0
Set the total volume of the batch
that needs to be pumped.
Units are based on unit selection
in SMARTFLOW setup wizard
84.02
TOTAL VOLUME
RESET
DISABLED [default]
ENABLE
Resets the total pumped volume
displayed in parameter 1.228. The
PS220 cannot be restarted once
the system volume is achieved
until the reset is completed.
1.228
TOTAL PMP
VOLUME
READ ONLY
Displays the total pumped volume in
the units selected with either the
SmartFlow Configuration Wizard, or
with the Process Control
Configuration Wizard.
Local Lock
The PumpSmart PS220 has the capability of “locking” the Local/Remote buttons function. Once activated a user cannot
switch the drive from Remote to Local. To activate, access Parameter 19.17. “Yes” activates the “Local Lock” Function. It
is “Unlocked “by default with the choice of “No”.
Language
English American is the default language. On the PumpSmart PS220. Units of power are in HP. English (UK)
notation refers to British English, with units of power in kW.
The language selection between English (US) and English (UK) is configured in the Basic Startup Wizard upon
first powering up of the drive. Once a selection is made, the language selection option does not reappear in the
basic startup wizard. It can be changed with Parameter 96.01
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...