PS220 Configuration & Operation Guide
137 PS220
Function & F
eatures
Input L1
Input L2
Input L3
Red Probe
on UDC+
terminal and black
probe on the Input
terminal
Black Probe
on
UDC+ terminal and
red probe on the
Input terminals
Red Probe
on UDC-
terminal and black
probe on the Input
terminal
Black Probe
on UDC-
terminal and red
probe on the Input
terminals
Rectifier
The rectifier circuit
converts the incoming
AC voltage to rippled
DC
DC Link
The inductor and
capacitor behave like a
Low pass filter and
smoothen out the
rippled DC voltage
c
o
n
t
r
o
l
Inverter
IGBT’s convert the DC
voltage to a Pulse
width modulated
output waveform
Motor
UDC+
UDC-
L1
L2
L3
T1U
T2V
T3W
Notes:
The above test is used to verify if the input rectifier bridge on the drive is faulty.
Possible causes of failure:
• High input voltage spikes or surges can cause damage to input bridge.
• A Short Circuit on the output could cause damage the output bridge.
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...