PS220 Configuration & Operation Guide
253 PS220
Fault T
racing
Table A2 - 2
All PS220 Pump and System Fault Messages
Each message on the keypad displays the warning name as well as and unique code
on the Keypad and store the event in the Event Log.
CODE
(HEX)
WARNING
CAUSE
WHAT TO DO
E100
DRY RUN
(PROGRAMMABLE FAULT
FUNCTION 79.10)
The pump is operating in a
dry running, or Dead Head
condition.
•
Check parameter 79.11 for correct vale.
•
If using a flow Meter check the electrical meter outputs
value.
•
Re-tune SmartFlow.
•
Check Pump for wear
•
See Pump Protect E106 for additional remedies
E101
COND 1LO ALARM
(PROGRAMMABLE FAULT
FUNCTION 80.07)
The signal level for Condition
1 has fallen below the 80.09
COND 1 ALAMRM LIM LO.
•
Investigate cause of condition
•
Check parameter settings of 80.07 and 80.08
•
Check Sensor if installed.
E102
COND 1 HI ALARM
(PROGRAMMABLE FAULT
FUNCTION 80.07)
The signal level for Condition 1
has exceeded the 80.08
COND 1 ALAMRM LIM HI.
•
Investigate cause of condition
•
Check parameter settings of 80.07 and 80.09
•
Check Sensor if installed.
E103
COND 2 LO ALARM
(PROGRAMMABLE FAULT
FUNCTION 80.13)
The signal level for Condition 2
has fallen below 80.15 COND
2 ALAMR LIM LO
•
Investigate cause of condition.
•
Check parameter settings of 80.13 and 80.14
•
Check Sensor if installed.
E104
COND 2 HI ALARM
(PROGRAMMABLE FAULT
FUNCTION 80.13)
The signal level for Condition 2
has exceeded 80.14 COND 2
ALARM LIM HI
•
Investigate cause of condition.
•
Check parameter settings of 80.13 and 80.15 for the correct
value.
•
Check Sensor if installed.
E105
PUMP CLEANING RETRY
The Pump clean sequence
failed to unclog the pump
within the maximum number
of retries set in parameter
83.18.
•
Run additional cleaning sequences.
•
Dismantle pump and clean manually
E106
PUMP PROTECT
(PROGRAMMABLE FAULT
FUNCTION 79.01)
The actual process value is
lower than protection limit
•
Open the suction valve.
•
Check suction line for blockages.
•
The Foot valve not opening on suction lift applications.
•
Pump is not primed.
•
Pump is air locked, purge air from system.
•
Check discharge piping for breaks or excessive leaks.
•
Check for excessive amount of entrained air in suction system
•
Check for additional discharge line branches that may have
been added to piping.
•
Check discharge piping static height compared to TDH output of
the pump.
•
Transmitter may have failed showing a “Low Value”
E107
SMARTFLOW OVERFLOW
Error in the SmartFlow
calculation routine
•
Check Smartflow input parameters in group 77
•
Perform another Smartflow tune.
•
Contact the PumpSmart application team.
E108
OVER PRESSURE
Pump is running at a pressure
above requested.
•
This may happen if the drive minimum speed is set too high
relative to the speed required to make set-point pressure. Adjust
minimum speed down as required.
E109
TUNE TIMED OUT
The Smartflow tune unable
to be completed within 35
seconds.
•
Drive needs to be in “Remote” Control.
•
Check pump is not current limited and achieve the required
speed for the tune process.
•
See notes in the Configuration manual for Smartflow Tune.
E10A MIN FLOW FAULT
(PROGRAMMABLE FAULT
FUNCTION 79.08)
The pump is operating below
the safe continuous flow rate
set in 79.09.
•
Open the suction valve.
•
Check suction line for blockages.
•
The Foot valve not opening on suction lift applications.
•
Pump is not primed.
•
Pump is air locked, purge air from system.
•
Check discharge piping for breaks or excessive leaks.
•
Check for excessive amount of entrained air in suction system
•
Transmitter may have failed
•
Check for additional discharge line branches that may have
been added to piping.
•
Check discharge piping static height compared to TDH output of
the pump.
E10B
PUMP JAMMED
Pump is clogged
•
Run additional cleaning sequences.
•
Dismantle pump and clean manually.
E10D BASIC PUMP PROTECTION
(PROGRAMMABLE FAULT
FUNCTION 79.01)
The Pump is running at full
speed and not able to achieve
the set-point.
•
Open the suction valve.
•
Check suction line for blockages.
•
The Foot valve not opening on suction lift applications.
•
Pump is not primed.
•
Pump is air locked, purge air from system.
•
Check discharge piping for breaks or excessive leaks.
•
Check for excessive amount of entrained air in suction system
•
Check for additional discharge line branches that may have
been added to piping.
•
Check discharge piping static height compared to TDH output of
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...