PS220 Configuration & Operation Guide
PS220 266
Parameter
Listing
GROUP 7
SYSTEM INFORMATION
Reference the ACS880 Firmware Manual for detail
7.03
ABB ACS 880 DRIVE ID
Defines the PS220 Hardware Example: ACS880-01-04A6-2
7.05
ABB ACS 880 FIRMWARE
Defines the installed ABB Firmware Version. Example. 3.11.6.1
7.23
ITT APPLICATION
Defines the ITT M&C Application Firmware running.
7.30
PUMPSAMRT VERSION
Defines the PS220 installed Firmware version running.
GROUP 10
DIGITAL INPUT AND RELAY
OUTPUT STATUS
DESCRIPTION
10.01
DI STATUS
Displays the electrical status of digital inputs DIIL and DI6 to DI1. Bits 0 to 5 reflect the status of DI1 to DI6. Bit 15
reflects the status of the DIIL input. Example: 100000000000001. DIL is on (All of the way to the left), and DI1 is
on. (all the way to the right) This parameter is read-only.
10.21
RO STATUS
Status of the relay outputs. Viewed from left to right. RO1 is on the far right. 0000 is the format. Example: 00000001b
= RO1 is energized, RO2…RO8 are de-energized.
10.XX
Parameters
not shown
Refer to the ABB ACS880
Firmware manual
Reference the ABB ACS880 Firmware Manual for parameter definition. All ACS880 parameters may not be
supported.
GROUP 11
STANDARD DIO, FI, FO
DESCRIPTION
11.XX
Parameters
not shown
Refer to the ABB ACS880
Firmware manual
Reference the ABB ACS880 Firmware Manual for parameter definition. All ACS880 parameters may not be
supported.
GROUP 12
ANALOG INPUTS
DESCRIPTION
12.01
AI TUNE
Triggers the analog input tuning function. Connect the signal to the input and select the appropriate tuning
function.
12.03-12.05
AI SUPERVISION FUNCTIONS
See Configuration Manual
12.11
AI1 ACTUAL VALUE
Displays the value of analog input AI1 in mA or V (depending on whether the input is set to current or voltage by a
hardware setting). (0-22mA)
12.12
AI1 SCALED VALUE
Displays the value of analog input AI1 after scaling. This parameter is read only. (0-32767.000)
12.15
AI1 UNIT SELECTION
Selects the unit for readings and settings related to analog input AI1. Note: This setting must match the
corresponding hardware setting on the drive control unit. See Basic Wiring drawing in appendix A4. (mA or V)
12.17
AI1 MIN
Defines the minimum value for analog input AI1. Set the value actually sent to the drive when the analog signal
from the external source / transmitter is at its minimum setting. (0-22mA or 0-10V)
12.18
AI1 MAX
Defines the maximum value for analog input AI1. Set the value actually sent to the drive when the analog signal
from the external source / transmitter is at its maximum setting. (0-22mA or 0-10V)
12.19
AI1 SCALED AT AI1 MIN
Defines the real internal value that corresponds to the minimum analog input AI1 value defined by parameter
12.17 AI1 min. (0-32768.000)
12.20
AI1 SCALED AT AI1 MAX
Defines the real internal value that corresponds to the maximum analog input AI1 value defined by parameter 12.18
AI1 max. (0-32768.000)
12.21
AI2 ACTUAL VALUE
Displays the value of analog input AI2 in mA or V (depending on whether the input is set to current or voltage by a
hardware setting). This parameter is read-only. (0-22.000mA or 0-10.00V)
12.22
AI2 SCALED VALUE
Displays the value of analog input AI2 after scaling. This parameter is read-only. (0-32767.000)
12.25
AI2 UNIT SELECTION
Selects the unit for readings and settings related to analog input AI2.
Note: This setting must match the corresponding hardware setting on the drive control unit (see the hardware
manual of the drive). Control board reboot (either by cycling the power or through parameter 96.08 Control board
boot) is required to validate any changes in the hardware settings. (mA or V)
12.27
AI2 MIN
Defines the minimum value for analog input AI2. Set the value actually sent to the drive when the analog signal is
at its minimum setting. (0-22mA or 0-10V)
12.28
AI2 MAX
Defines the maximum value for analog input AI2. Set the value actually sent to the drive when the analog signal is
at its maximum setting. (0-22mA or 0-10V)
12.29
AI2 SCALED AT AI2 MIN
Defines the real value that corresponds to the minimum analog input AI2 value defined by parameter 12.27 AI2
min. (0-32768.000)
12.30
AI2 SCALED AT AI2 MAX
Defines the real value that corresponds to the maximum analog input AI2 value defined by parameter 12.28 AI2
max. (0-32768.000)
GROUP 13
ANALOG OUTPUTS
DESCRIPTION
13.11
AO1 ACTUAL VALUE
Displays the value of AO1 in mA. This parameter is read-only. (0.000-22.000mA)
13.12
AO1 SOURCE
Selects a signal to be connected to analog output AO1. Alternatively, sets the output to excitation mode to feed a
constant current to a temperature sensor. Default source is Motor Speed Used.
13.16
AO1 FILTER TIME
Defines the filtering time constant for analog output AO1 in seconds. Default value is 0.100 seconds.
13.17
AO1 SOURCE MIN
Defines the real minimum value of the signal that corresponds to the minimum required AO1 output value. This is
the engineering unit value for the minimum current value defined in parameter 13.19. (-32768.0 – 32768.0)
13.18
AO1 SOURCE MAX
Defines the real maximum value of the signal that corresponds to the maximum required AO1 output value. This is
the engineering unit value for the maximum current value defined in parameter 13.20. (-32768.0 – 32768.0)
13.19
AO1 OUT AT AO1 SRC MIN
Defines the minimum output current value for analog output AO1. (0-22.000mA)
13.20
AO1 OUT AT AO1 SRC MAX
Defines the minimum output current value for analog output AO1. (0-22.000mA)
13.21
AO2 ACTUAL VALUE
Defines the maximum output current value for analog output AO1. (0-22.000mA)
13.22
AO2 SOURCE
Selects a signal to be connected to analog output AO2. Alternatively, sets the output to excitation mode to feed a
constant current to a temperature sensor. Default source is Motor Current.
13.27
AO2 FILTER TIME
Defines the filtering time constant for analog output AO2 in seconds. Default value is 0.100 seconds.
13.27
AO2 SOURCE MIN
Defines the real minimum value of the signal that corresponds to the minimum required AO2 output value. This is
the engineering unit value for the minimum current value defined in parameter 13.29. (-32768.0 – 32768.0)
13.28
AO2 SOURCE MAX
Defines the real maximum value of the signal that corresponds to the maximum required AO2 output value. This is
the engineering unit value for the maximum current value defined in parameter 13.30. (-32768.0 – 32768.0)
13.29
AO2 OUT AT AO2 SRC MIN
Defines the minimum output value for analog output AO2. (0-22.000mA)
13.30
AO2 OUT AT AO2 SRC MAX
Defines the maximum output value for analog output AO2. (0-22.000mA)
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...