PS220 Configuration & Operation Guide
PS220 262
Parameter
Listing
1.70
AMBIENT TEMPERATURE %
Measured temperature of incoming cooling air. The amplitude range of 0…100%
corresponds to 0…60 °C or 32…140 °F. See also 01.31 Ambient temperature. -200.00-
200.00%
1=1%
1.71
STEP-UP MOTOR CURRENT
Estimated motor current in A when a step-up transformer is in use. The value is calculated
from parameter 01.07 using the step-up transformer ratio (95.40) and sine filter values 99.18
and 99.19. 0.00 - 30000.00 A
See
parameter
46.05
1.72
U-PHASE RMS CURRENT
U-phase RMS current. 0.00 - 30000.00 A
1.73
V-PHASE RMS CURRENT
V-phase RMS current. 0.00 - 30000.00 A
1.74
W-PHASE RMS CURRENT
W-phase RMS current. (0.00 - 30000.00 A
1.200
FLOW REF
Reference for flow control. 0 - 100000
1
=
1
1.201
FLOW ACTUAL
Actual flow feedback 0 - 100000
1.202
PRESS REF
Reference for pressure control -1000000 - 10000000
1.203
PRESS ACTUAL
Actual pressure feedback -10000000 - 21474836.47
1.204
LEVEL REF
Reference for level control -21474836.47 - 21474836.47
1.205
LEVEL ACTUAL
Actual level feedback -10000000 -100000
1.206
TEMP REF
Reference for temperature control -2000 - 2000
1.207
TEMP ACTUAL
Actual temperature feedback -2000 - 2000
1.208
PUMP SPEED
Actual speed of pump, rpm. Will be different than motor speed if belt drive or gear drive is
used. 0-10000
1.209
SPECIFIC GRAVITY
Specific gravity of pumped liquid 0.00 - 100
1.210
VISCOSITY
Value of viscosity being used by SmartFlow 0.00 - 60000
1.212
SETPOINT 1
Setpoint #1 value. Limited by setpoint Min and Setpoint Max.
1.213
MULTIPUMP FEEDBACK
Summed process feedback of all drives as seen by drive in a Multipump system. Typically
used in Multipump Flow control. -10000000.0 – 100000000.0
1.214
MULTI VAR SETPOINT
Calculated setpoint calculated by the PS220. Result setpoint when influenced by the second
variable of Multivariable control.
1.215
SETPOINT 2
Setpoint #2 value. Limited by setpoint Min and Setpoint Max.
1.216
PROC TX2
Current value of process transmitter 2. 10000000.00 - 1000000.00
1.217
SMARTFLOW
PS220’s calculated Pump flow output 0 – 100000.0
1.218
SMART TDH
PS220’s calculated total dynamic head. 10000000.00 – 10000000.00
1.219
BEP
Current operating efficiency as compared to best efficiency point 0.0 – 20000%
1.220
FLOW ECONOMY
A relative measure of pumping efficiency. 0- 1000000 GPM/kW
1.223
ENERGY SAVINGS
Calculated energy savings since last reset for Energy Savings Option 1 or 2. 0.00 – 1000000
US$
1.224
RUN TIME
Elapsed time counter in hours since last reset. Runs whenever drive is turning the motor. 0.0
– 1000000 Hours
1.225
KWH SINCE RST
KWh counter, kWh since last reset. 0.0 – 1000000 KWh
1.226
PMP CLN RUN TIME
(No Longer used)
Run time for the pump cleaning sequence when runtime is selected. No longer used.
1.227
SYSTEM FLOW
Total flow rate for all pumps running in a Multipump system. -100000000.0 –
100000000.0
1.228
TOTAL PMP VOLUME
Totalized Flow value for a single pump. -100000000.0 – 100000000.0
1.229
TOTAL SYSTEM VOLUME
Total flow of all pumps when operated in Multipump. -100000000.0 – 214748364.7
1.230
PROC TX1
Signal value of the Primary Process transmitter. -1000000.0 – 1000000.0
1.231
MULTIPUMP SETPOINT
Setpoint seen by all of the drives in a Multipump system. -1000000.0 – 1000000.0
1.233
START COMMAND
Indication of whether a start command has been received by the PS220 or not. 0-1
1.234
EXT SETPOINT 1
External Setpoint 1 ( Analog signal) sent to the drive SCALING IS per the AI assigned
1.235
EXT SETPOINT 2
External Setpoint 2 ( Analog signal) sent to the drive SCALING IS per the AI assigned
1.236
WAKEUP CONDITION 2 VALUE
Wake up value for condition 2 if alarm response is set to sleep. -1000000.00 –
1000000.00
1.237
WAKEUP CONDITION 1 VALUE
Wake up value for condition 1 if alarm response is set to sleep. – 1000000.00 –
1000000.00
1.238
MULTIPUMP RUNTIME
Provides the length of time this drive pump has run in Multipump. Does not include
sleeping. 0 – 65535.IE
GROUP 3
INPUT REFERENCES
DESCRIPTION
Scaling
3.01
PANEL REFERENCE
Reference given from the control panel or PC tool. (-100000.00-1000000.00)
1=10
3.02
PANEL REFERENCE 2
Remote reference given from the control panel or PC tool. (-30000.00-30000.00)
1=10
3.05
FB A REFERENCE 1
Reference 1 received through fieldbus adapter A. (-100000.00-100000.00)
1=10
3.06
FB A REFERENCE 2
Reference 2 received through fieldbus adapter A. (-100000.00-100000.00)
1=10
3.07
FB B REFERENCE 1
Reference 1 received through fieldbus adapter B. (-100000.00-100000.00)
1=10
3.08
FB B REFERENCE 2
Reference 2 received through fieldbus adapter B. (-100000.00-100000.00)
1=10
3.09
EFB B REFERENCE 1
Scaled reference 1 received through the embedded fieldbus interface. The scaling is defined
by 58.26 EFB ref1 type. (-30000.00-30000.00)
1=10
3.10
EFB B REFERENCE 2
Scaled reference 2 received through the embedded fieldbus interface. The scaling is defined
by 58.27 EFB ref2 type. (-30000.00-30000.00)
1=10
3.11
DDCS CONTROLLER REF 1
Reference 1 received from the external (DDCS) controller. The value has been scaled
according to parameter 60.60 DDCS controller ref1 type.
See also section External controller interface. (-30000.00-30000.00)
1=10
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...