PS220 Configuration & Operation Guide
231 PS220
Function & F
eatures
2. The settings for Parameters 37.11 through 15 should not have to be changed for a 1780 RPM
motor. They will need to be change for motors of lower or higher full load synchronous speeds
(1180 RPM and 3550 RPM). The recommendations are as follows:
37.11 = 8.5% of Full Load speed
37.12 = 42% of Full Load speed
37.13 = 72% of Full Load speed
37.14 = 84% of Full Load speed
37.15 = 100% of Full load speed
3. Parameters not mentioned do not apply to this function
4. Configure the time period before the drive will react when an underload condition exits. The
Default is 20 Seconds. The Ranges is 0-10,000 seconds.
Parameter
Description
Default in
RPM of the
Motor
Recommendation
Notes
37.11
1st X Axis
Intersection
Point
150
S e e N o t e s
Should be
10% of Max
Motor Speed
37.12
2nd X Axis
Intersection
Point
750
S e e N o t e s
Should be
50% of Max
Motor Speed
37.13
3rd X Axis
Intersection
Point
1290
S e e N o t e s
Should be
72% of Max
Motor Speed
37.14
4th X Axis
Intersection
Point
1500
S e e N o t e s
Should be
83% of Max
Motor Speed
37.15
5th X Axis
Intersection
Point
1800
S e e N o t e s
Should be
100% of Max
Motor Speed
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...