PS220 Configuration & Operation Guide
PS220 128
Functions &
Features
Auto Reset (VFD)
The PumpSmart PS220 can be configured to automatically reset specific VFD related faults. The drive will follow a routine
of faulting, waiting, and automatically resetting up to five time within a pre-determined amount of time. After this time if
the condition(s) still exists the PumpSmart PS220 drive will issue a “Hard” fault and will have to be manually restarted.
Please refer to the Pump and VFD Protection Wizard for more specific detail on how to set these parameters with your
pumping system. To access this wizard from the home view, follow the path: Menu>PS220 Configuration> Pump &VFD
Protection>VFD Protection
Parameter
Name
Value/Range
Note
31.12
AUTO RESET SELECTION
0000 [default]
Selects faults
that are
automatically
reset. The
parameter is a
16-bit word with
each bit
corresponding
to a fault type.
Whenever a bit
is set to 1, the
corresponding
fault is
Automatically
reset.
31.14
NUMBER OF TRIALS
0 – 5
0 [default]
Defines the
number of
automatic
resets allowed.
A setting of
zero disables
this function.
31.15
TOTAL TRIAL TIME
1 – 600 sec
180 [default]
Defines the
allowable time
period for
counting and
resetting a
fault. This
parameter
limits the
number resets
in Parameter
31.14 which can
occur within
this time period.
31.16
DELAY TIME
0 – 120 sec
0 sec [default]
Defines the
time that the
PS220 will wait
before at-
tempting an
auto reset of
the VFD FAULTS
selected in
31.12
BIT
Fault
0
OVERCURRENT
1
OVERVOLTAGE
2
UNDERVOLTAGE
3
AI SUPERVISION
4
SUPPLY UNIT
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...