PS220 Configuration & Operation Guide
283 PS220
(Externally Sourced)
Multiple Transmitters/Jumpers
Example-2-wire process transmitter and remote 4-20 mA reference
(setpoint) signal from PLC or DCS.
I
Example-Externally powered process and reference signal
connections. These signals must provide 4 - 20mA, or 0 - 10VDC
to the Analog inputs.
Expose the shield of the control wire cable
and slide a conductive clamp onto the cable.
Connect clamp to the grounding lugs in the
conduit box.
JUMPERS
When PumpSmart is powering a 2-wire process transmitter, the current loop must be
completed with a jumper from the PS220 analog input negative terminal to XD24-5. In
cases where multiple transmitters are powered you may jumper between each analog
input negative then to XD24-5.
Jumper
Example: Discharge Pressure Control
Application w/ Suction Pressure
PT
NOTICE
All instrumentation shielding must
be terminated at grounding lugs
provided by the PS220. Do not
terminate Shielding at sensor end.
K05637A
PS220 Basic Wiring PS220
XAI
Terminal Block
+VREF
1
2
3
4
5
6
7
-VREF
AI1+
XD24
Terminal Block
1
2
3
4
5
+24VD
DICOM
+24VD
DIOGND
Example: Pressure Control
Application
PS220 BASIC WIRING
Instruments Loop Powered By PumpSmart
Example: Pressure Control Application
Control
connections
Description
2 differential analog
inputs(XAI)
"Green"
Current input: 4(0) to 20 mA
R
IN
: 100 ohm
Voltage input: 2(0) to 10 V
R
IN
: 200 Kohm
Resolution: 11 bit + sign bit
2 differential analog
outputs (XAO) "Green
0 to 20 mA, R
LOAD
<500 ohm
Frequency range: 0-300 Hz
Resolution: 11 bit + sign bit
6 digital
inputs (XDI) "Blue"
Input type: NPN/PNP (DI1 to DI5), NPN (DI6)
DI6 (XDI:6) can alternatively be used as an
input for a PTC thermistor
Digital input interlock
(XD24) "Blue"
Input type: NPN/PNP
2 digital inputs/outputs
(XDIO) "Blue"
As input:
24 V LOGIC LEVELS:
"0" <5 V, "1"> 15 V
R
IN
: 2.0 Kohm
Filtering:0.25 ms
As output:
Total output current from 24 V DC is limited to 200 mA
Can be set as pulse train input and output
3 relay outputs (XRO1,
XRO2, XRO3) "Red"
250 V AC/30 V DC, 2A
Safe torque-off (XSTO)
"Gold"
For the drive to start, both connections must be closed.
Drive-to-drive link
(XD2D) "Gray"
Physical layer: EIA-485 (RS485)
Built-in Modbus
Not Accessable
Assistant control panel/
PC tool connection
Connector:RJ-45
XSTO
XDI
XDIO
XR03
XD24
XPOW
XAI
J1,J2
XAO
XD2D
XRO2
XRO1
X204
X203
X12
X205
X202
X208
X13
J3,J6
Jumpers are installed at the factory. If using safe torque-off remove
jumpers and replace with appropriate contact blocks or safe torque-off
switch. Note, both inputs must be closed for drive to run motor. See
Hardware Manual for detail on wiring Safe Torque-Off.
!! NOTE !!
+24VI
External 24 VDC Power Input
24VDC 2A Maximum
GND
1 VREF(+)
AI Reference Voltage
10VDC
2
VREF(-)
3
AGND
AI Reference Ground
10VDC Ref
4
4-20mA Analog Input(1)
Proc Trans 1-Primary Control Instrument
5
6
4-20mA Analog Input(2)
Proc Trans 2-Secondary Control Instrument
7
1
AO1
Motor speed rpm 0 to 20 mA, R
L
<500 ohm
2
AGND
3
AO2
Motor current 0 to 20 mA, R
L
<500 ohm
4
AGND
1
B
Drive-to-drive link or built-in Modbus
2
A
3
BGND
11
NC
Ready
250 V AC/30 V DC
2A
12
COM
13
NO
NC
Running
250 V AC/30 V DC
2A
22
COM
23
NO
NC
Faulted (-1)
250 V AC/30 V DC
2A
32
COM
33
NO
1
DIIL
E Stop/Drive Permissive
2 +24VD +24 V DC 200 mA
3
DICOM Digital input ground
4 +24VD +24 V DC 200 mA
5 DIOGND Digital input/output ground
1
DI01
Output: Ready
2
Output: Running
1
D
I
1
2 Wire Start/Stop (Auto)
2
Hand/Jog
3
Dual Setpoint
4
Secondary Pump Protect A
5
Secondary Pump Protect B
6
Fault Reset
1
OUT1
Safe torque-off. Both circuits must be closed for the drive to
start.
2
SGND
3
IN1
4
X12
Safety functions module connection
X13
Control panel connection
X205 Memory unit connection
Reference voltage and analog inputs
XAI
XRO1, XRO2, XRO3 Relay outputs
External power input
Safe torque-off
XPOW
XAO
Analog outputs
Drive-to-drive link
XD24
XDIO
XD2D
Digital interlock
Digital input/outputs (Examples)
Digital Inputs (Examples)
XDI
XSTO
2
1
On Board Connections
J1, J2
1
2
Key:
Metal Pin Pair
Jumpers
Analog Input Current/Voltage Configuration
21
31
PT
PT
U
X202
X203
X204
Fibre optic module connection
Fieldbus module connection
Analog IO Extension module connection
XPOW
XAI
XAO
XD2D
XRO1
XRO2
XR03
XD24
XDIO
XDI
XSTO
Sheild
Grounding
Clamp
Sheilded Control
Wire
J3
Drive-to-drive link termination switch
J6
Ground selection switch
AI1-
AI2+
AI2-
D
I
2
D
I
3
IN2
DI02
XAI
Terminal Block
+VREF
1
2
3
4
5
6
7
-VREF
AI1+
AI1-
AI2+
AI2-
DIIL
XD24
Terminal Block
1
2
3
4
5
+24VD
DICOM
+24VD
DIOGND
DIIL
XAI
Terminal Block
+VREF
1
2
3
4
5
6
7
-VREF
AI1+
AI1-
AI2+
AI2-
AI1+
AI1 -
AI2+
AI2 -
D
I
4
D
I
5
D
I
6
AI1
AI2
AI1
AI2
AI2
AI1
I=Current
U=Voltage
PT
The D L is a drive permissive and must be
closed (24Vdc) for the drive to operate. A
jumper is installed at the factory. If using the
DIIL drive permissive, remove the jumper and
replace with appropriate contact block.
X208 Cooling fan 1 connection
(Externally Sourced)
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...