PS220 Configuration & Operation Guide
279 PS220
Parameter
Listing
83.02
REQ P CLEAN SEQ
Applicable only when 83.01 is set
to PS220.
Defines what triggers the request of the pump
cleaning sequence.
NOT SEL (DEFAULT)
Disable the Automatic execution of the PCS
TORQ
The request is triggered when 1.10 MOTOR
TORQUE exceeds the value set in 83.03 TORQ
REQ for the 83.04 TON REQ.
Time of Day
This request is triggered when the time of day is
reached,
TORQ OR TIME of Day
This request is triggered by either motor torque
or run time.
83.03
TORQUE REQ
0.0-200.0%
120% [default]
Defines the motor torque threshold value in %
above nominal motor torque to trigger the
execution of the pump cleaning sequence.
83.04
TON REQ
0-100 Seconds 5s [default]
Time period before the pump cleaning sequence
can be triggered once the threshold torque is
reached,
83.05
RUN TIME REQ
24-hour clock time in Hours,
Minutes, and seconds.
Defines the time of the day at which the pump
cleaning sequence executes automatically.
83.06
NUM OF CYCLES
1-10
2 [default]
Defines the number of cycles the pump cleaning
sequence can execute.
83.07
FWD RUN SPD
0.0-100.0%
100% [default]
Defines the forward running speed in % of
parameter 30.12, MAXIMUM SPEED.
83.08
FWD RUN TIME
0.0-100.0 Seconds
7s [default]
Defines the forward running time of the
pump cleaning sequence.
83.09
FWD RUN ACC
0.0-100.0 Seconds
1s [default]
Defines the forward acceleration rate during the
execution of the cleaning cycle.
83.10
FWD RUN DEC
0.0-100.0 Seconds
2s [default]
Defines the forward deceleration rate during the
execution of the cleaning cycle.
83.11
ZERO SPEED PAUSE
0.0-100.0 Seconds
7s [default]
Defines the pause time during the pump
cleaning sequence that the pump does not run
when switching from forward to reverse
rotation.
83.12
REV RUN SPD
0.0-100.0%
80% [default]
Defines the reverse running speed in % of
parameter 30.12, MAXIMUM SPEED.
83.13
REV RUN TIME
0.0-100.0 Seconds
7s [default]
Defines the reverse running time of the pump
cleaning sequence.
83.14
REV RUN ACC
0.0-100.0 Seconds
2 Seconds [default]
Defines the forward acceleration rate during the
execution of the cleaning cycle.
83.15
REV RUN DEC
0.0-100.0 Seconds
01Seconds [default]
Defines the reverse deceleration rate during the
pump cleaning sequence.
83.16
SEQUENCE TIMER
0-100 Seconds
30 Seconds [default]
Defines the value in seconds, after which a pump
cleaning sequence retry is attempted.
83.17
SEQUENCE COUNTER
0-10
5 [default]
The number of times the PCS will run sequentially
when executed.
83.18
SEQUENCE EXCEED
Action and message displayed when the number
of sequences in 83.17 has been completed and
the torque value monitored is still at or above the
value in 83.03. The default is FAULT.
DISABLED
The SEQUENCE EXCEED function is disabled and
there is no limitation on the number of PCS
requests and executions.
WARNING
The Keypad displays a warning PUMP CLOGGED
and the PCS function is disabled. The drive
continues to function in its normal configured
state.
FAULT [default]
The drive faults and must be manually reset. The
Keypad displays a PUMP CLOGGED fault
message.
83.19
SNORE TIME
The elapsed runtime before the Snore function is activated. Range: 0 – 10,000 hrs. Default is
zero hours which disables this function.
83.20
TORQUE COEFF
Defines the torque coefficient setting needed to activate the snore
function. Range: 0.00 – 1.00.
83.21
PIPE CLEAN ENABLE
Enables the pipe clean function. The pump will ramp to maximum speed for the cycle time
and then return to normal operation.
DISABLED [DEFAULT]
Disables the pipe clean function.
ENABLE ON START
Enables the pipe clean function on every start command.
ENABLE ON TIME
Enables the pipe clean function based on elapsed time from 83.22.
83.22
PIPE CLEAN TIME INTERVAL
The elapsed runtime hours that will enable the Pipe Clean Function when enabled. Once the
setting is reached the pipe clean function is started. Range 0 – 10,000hrs. 100 hours
(default)
83.23
PIPE CLEAN CYCLE TIME
The time spent at maximum speed during the Pipe Cleaning cycle. Range 0 - 1800 sec.
Default is 600 seconds
83.24
PIPE FILL ENABLE
Enable the pipe fill function
DISABLE [DEFAULT]
Disable the pipe fill function
ENABLE
Enable the pipe fill function. (DI6 control does not function)
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...