PS220 Configuration & Operation Guide
197 PS220
Function & F
eatures
NOTE:
This message may appear as you configure this function with the Wizard. Select “Hide” and continue. This
message is the result of the Digital Input is showing “Open”. It may be wired incorrectly, or the device is in an
“Open-state”. This is quite normal. Select “Hide” to continue.
3. Configure the Digital Input to be used.
Notes:
Digital Input 4 (DI4) is the recommended selection for Secondary Protection A
Digital Input 5 (DI5) is the recommended selection for Secondary Protection B
Please refer to the “Protection Options” in this manual for the details of the responses available with Second-
ary protection
Any unused Digital Input (DI) can be configured for use with this function. Please check the settings of the
Digital Inputs currently in use by going to: Menu>Parameters> Complete List>Scroll down to Group 76>
Select and View 76.09 through 76.14. If available “NOT SELECTED” will be displayed. An Extension Card will
need to be added and configured if they are all in use.
The Table below list all of the Parameters used with the Secondary Protection Wizard functionality. Parameters
may be manually configured if required for a particular application.
79.14
SECONDARY PROTECT A
Loss of the Digital Input configured for this Function.
DISABLED [DEFAULT]
Protection is disabled
ALARM
The PS220 generates a warning only “Secondary Protect A”. No further action is
taken.
ALARM AND CONTROL
The PumpSmart PS220 will indicate a “Secondary Protect A” warning message,
after the response delay time has expired. The event will be stored in the Event
Log. The PS220 will then respond based on the Protections Options
79.15
SECONDARY PROTECT B
Loss of the Digital Input configured for this Function.
DISABLED [DEFAULT]
Protection is disabled
ALARM
The PS220 generates a warning only “Secondary Protect B”. No further action is
taken.
ALARM AND CONTROL
The PumpSmart PS220 will indicate a “Secondary Protect B” warning message,
after the response delay time has expired. The event will be stored in the Event
Log. The PS220 will then respond based on the Protections Options.
GROUP 76
ANALOG I/O CONFIG
DESCRIPTION
76.09
DI1
Selects the Digital input 1 function
76.10
DI2
Selects the Digital input 2 function
76.11
DI3
Selects the Digital input 3 function
76.12
DI4
Selects the Digital input 4 function
76.13
DI5
Selects the Digital input 5 function
76.14
DI6
Selects the Digital input 6 function
76.15
DIO1
Selects whether DIO1 is used as a digital output or input, or a frequency input.
76.16
DIO2
Selects whether DIO2 is used as a digital output or input, or a frequency input.
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...