PS220 Configuration & Operation Guide
PS220 276
Parameter
Listing
79.15
SECONDARY PROTECT B
Loss of the Digital Input configured for this Function.
DISABLED [DEFAULT]
Protection is disabled
ALARM
The PS220 generates a warning only “Secondary Protect B”. No further action is taken.
ALARM AND CONTROL
The PumpSmart PS220 will indicate a “Secondary Protect B” warning
message, after the response delay time has expired. The event will be stored
in the Event Log. The PS220 will then respond based on the Protections
Options.
79.16
CONFIG MIN SPEED
The selection to allow the PS220 to run at either its Minimum Speed, or at Zero Speed (0)
when required for the Functionality as configured.
SPEED = 0
The drive will stay at zero (0) speed when the “Alarm and Control” functional routine is
actively running for “Pump Protection”. This also will allow the “Sleep Function” to activate.
SPEED = MIN SPEED
The PS220 will remain at minimum speed when the “Alarm and control” functional routine
is actively running for Pump protection, or when the “Sleep Function” is disabled in PID
Control.
79.17
STP DELAY MIN SPD
The time period used with various PS220 functions where the drive will remain at minimum
speed. Functional Pump Protection and Control routines will continue as configured after
this time has expired.
GROUP 80 CONDITION MONITORING
DESCRIPTION
80.01
CONDITION STATUS
A 1 indicates the condition is active
BIT
FUNCTION DESCRIPTION
0
Enabled
1
Cond1 High Alarm
2
Cond1 High Warning
3
Cond1 Low Warning
4
Cond1 Low Alarm
5
Cond2 High Alarm
6
Cond2 High Warning
7
Cond2 Low Warning
8
Cond 2 Low Alarm
13
Sleep Active
14
Min Speed Active
Parameter Name
Value/Range
NOTES
80.04
COND 1 SOURCE
None [Default]
Flow Actual
Pressure Actual
Level Actual
Speed
Torque
Power
Current
Temperature
Actual
SmartFlow
PROC TRANS 1
PROC TRANS 2
Select the source of the signal to be monitored. The
source can either be from an external transmitter wired to
an available analog input or it can be an internal signal
as selected by the parameter number.
80.05
COND 1 WRN LIM HI
-10000 to +10000
0 [default]
The high value of the warning limit. A warning occurs if
the monitored signal rises above this value for longer
than the response delay. Inactive if set to 0.
80.06
COND 1 WRN LIM LO
-10000 to +10000
0 [default]
The low value of the warning limit. A warning occurs
if the monitored signal drops below this value for longer
than the response delay. Inactive if set to 0.
80.07
COND 1 ALARM
DISABLED [default]
Protection is inactive.
ALARM ONLY
Selecting ALARM ONLY will issue a Keypad message
showing that an ALRM LIM HI or ALRM LIM LO condition is
detected. No further action is taken.
MIN SPD
Selecting MIN SPD will issue a Keypad message
showing that an ALRM LIM HI or ALRM LIM LO
condition is detected and will drop to MIN SPEED. If
the alarm does not reset itself after the MIN SPD STP
DLY the PS220 will fault.
SLEEP
The PS220 will shut down and go into a sleep mode if
an ALRM LIM HI or ALRM LIM LO condition is
detected. It will “wake up” according to the value in
80.22.
FAULT
The PS220 faults if an ALRM LIM HI or ALRM LIM LO
condition is detected. A Keypad notice is issued
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...