PS220 Configuration & Operation Guide
169 PS220
Function & F
eatures
10. Configure the Stage/De-Stage Values for Pumps 2, 3 etc.
The default values are as shown. Validate all during commissioning.
11. Exit the Wizard and repeat for the remaining Pumps.
12. Follow instruction below:
Once you have completed the Multipump Configuration Wizard you MUST send a setpoint reference
change from the source selected in Basic Startup, from and to each and every drive. This will ensure that
the reference changes on each drive’s keypad display. It confirms that the PS220’s are communicating with
each other. It should take 3-4 seconds for this change to visibly register across all of the individual drive’s
keypads.
Parameter
Descrip
�
on
Default Se
�
ng
81.09
Stage 2 Value
98%
81.10
Stage 3 Value
98%
81.11
Stage 4 Value
98%
81.17
Stage 5 Value
98%
81.18
Stage 6 Value
98%
81.13
De-Stage 2 Value
75%
81.14
De-Stage 3 Value
85%
81.15
De-Stage 4 Value
92%
81.21
De-Stage 5 Value
94%
81.22
De-Stage 6 Value
98%
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...