PS220 Configuration & Operation Guide
199 PS220
Function & F
eatures
Parameter
Name
Value/Range
Notes
12.03
ANALOG INPUT SUPERVSION
FUNCTION
NO ACTION [default]
FAULT
WARNING
LAST SPEED
SPEED REF SAFE
Defines action taken upon failure of an analog
input. Failure messages indicate which input
channel has failed.
RECOMMENDATION IS FAULT
12.04
AI SUPERVISION SELECTION
Each corresponding bit allows selection of
minimum and maximum limit supervision. User
may enable/disable each of the limit types.
** = RECOMMENDATION IS FOR ALL BITS TO BE
CONFIGRED HIGH (1 vs 0 ) FOR ANY AI
CONNECTED
Parameter
Name
Value/Range
Notes
32.05
Supervision 1
Function
Both
Monitors both the Lower and Upper limits of the
Analog Signal selected
32.06
Supervision 1 Action
Fault
Faults the PS220 when either signal reaches the
thresholds noted in 32.09 and 32.10
32.07
Supervision 1 Signal
AI1 ( If Used)
The AI used
32.09
Supervision 1 Low
value
3.8
Any value below this threshold will trigger supervision
32.10
Supervision 1 High
value
20.2
Any value above this threshold will trigger
supervision
32.15
Supervision 2
Function
Both
Monitors both the Lower and Upper limits of the
Analog Signal selected
32.16
Supervision 2 Action
Fault
Faults the PS220 when either signal reaches the
thresholds noted in 32.09 and 32.10
32.17
Supervision 2 Signal
AI2 If Used)
The AI used
32.19
Supervision 2 Low
value
3.8
Any value below this threshold will trigger supervision
32.20
Supervision 2 High
value
20.2
Any value above this threshold will trigger
supervision
Bit Fault trigger
default Setting
0 AI1<MIN LIMIT
0
**
1 AI1>MAX LIMIT
0
**
2 AI2<MIN LIMIT
0
**
3 AI2>MAX LIMIT
0
**
Selecting the choice of “NO Action” may result in running a pump up to full speed. If using the
Multipump functionality it may run all of the additional pumps that have start commands initiated
to try to regulate to the process setpoint.
Содержание PumpSmart PS220
Страница 1: ...Configuration Operation Manual PumpSmart Control Solutions PS220 v6 05...
Страница 5: ...PS220 Configuration Operation Guide PS220 4 Getting Started THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 9: ...PS220 Configuration Operation Guide PS220 8 Basic Startup THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 22: ...PS220 Configuration Operation Guide 21 PS220 SmartFlow...
Страница 40: ...PS220 Configuration Operation Guide 39 PS220 Process Control THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 217: ...PS220 Configuration Operation Guide PS220 216 Functions Features This is an example of a typical Pump Performance Curve...
Страница 261: ...PS220 Configuration Operation Guide PS220 260 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 283: ...PS220 Configuration Operation Guide PS220 282 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 289: ...PS220 Configuration Operation Guide PS220 288 Ecodesign Regulation...
Страница 292: ...PS220 Configuration Operation Guide 291 PS220 Fuses heat dissipation chart...