PS220 Configuration & Operation Guide
PS220 86
M
ul
tiv
ari
ab
le
We suggest using diagrams like the one shown below:
In the above diagram, the set-point is 50psi. When the secondary process transmitter (TX2) is below 5ft
(LEVEL 1) of tank level, it will begin to scale back the set-point linearly from 50psig to 10psi (SP LO) at 2ft (LO
INTRCPT). When the secondary process transmitter (TX2) reaches 16ft of tank level (Level 2), it will increase the
set-point linearly from 50psi to 75psi (SP HI) at 18ft (HI INTRCPT).
Note:
To Disable this Functionality, you MUST re-run the Basic Startup and the Process Control Wizards.