17 COMMISSIONING
17.9 CONTROL SCHEMES
17
Instantaneous O/C Blocking:
1.
Select the
MAX NUMBER OF RECLOSURE SHOTS
to be 4. With Phase Inst OC 1 function selected as
Trip + AR
,
set the test set to a current level above the pickup of this element, and inject into a phase input. The relay
should trip and reclose 4 times. Turn off the current, reset the relay and close the breaker.
2.
Enable Phase Inst OC 1 Blocking for Reclosure Shot 1. Turn on the current. The relay should trip and
reclose once. The Shot in Effect display should show 1. The PICKUP indicator should be off. Once the
Autoreclose Reset Time has expired, the relay will then pickup, trip and reclose until lockout as the fault
current is still present. Turn off the current, reset the relay and close the breaker.
3.
Disable Phase Inst OC 1 Blocking for Reclosure Shot 1, and Enable for Reclosure Shot 2. Turn on the cur-
rent. Reclosure Shot 2 should not operate, and the PICKUP indicator will be off. Turn off the current and
reset the relay.
4.
Repeat procedure 3 using Phase Inst OC 1 Blocking for each of the 4 Reclosure Shot settings.
5.
Repeat steps 1-4 for each Instantaneous OC Blocking setpoint, disabling each Instantaneous OC element
before moving on to the next.
Raised Pickup of Time O/C Elements:
1.
Keep the Maximum Number of Reclosure Shots at 4. With the Phase Time OC 1 function selected as Trip
+ AR, set the test set to a current level above the pickup of this element. Turn off the current, reset the
relay and close the breaker.
2.
In Reclosure Shot 1 settings, select the Phase Time OC 1 Raised Pickup such that it brings the pickup
level just below the actual current that is being injected. Turn on the current. The relay should trip and
reclose 4 times.
3.
In Reclosure Shot 1 settings, select the Phase Time OC 1 Raised Pickup such that it brings the pickup
level just above the actual current that is being injected. Turn on the current. The relay should trip and
reclose once. The Shot in Effect display should show 1. The PICKUP indicator should be off. Once the
Autoreclose Reset Time has expired, the relay will then pickup, trip and reclose until lockout as the fault
current is still present. Turn off the current, reset the relay and close the breaker.
4.
Return Phase Time OC 1 Raised Pickup to 0 for Reclosure Shot 1, and set it to a level that is above the
actual current for Reclosure Shot 2. Turn on the current. Reclosure Shot 2 should not operate, and the
PICKUP indicator will be off. Turn off the current and reset the relay.
5.
Repeat procedure 4 using Phase Time OC 1 Blocking for each of the 4 Reclosure Shot settings.
6.
Repeat steps 1-5 for each Time OC Raised Pickup setpoint, disabling each Time OC element before mov-
ing on to the next.
Select Setpoint Group:
1.
Keep the Maximum Number of Reclosure Shots at 4. In Setpoint Group 1, Enable
PHASE TIME OC 1
to
Trip +
AR
. In Setpoint Group 2, Enable
PHASE TIME OC 2
to
Trip + AR
. In Setpoint Group 3, Enable
PHASE INST OC
1
to
Trip + AR
. In Setpoint Group 4, Enable
PHASE INST OC 2
to
Trip + AR
. Select the same pickup level for
each element.
2.
For Reclosure Shot 1 settings, set the
SELECT SETPOINT GROUP
setpoint to
Group 2
. Similarly, set it to
Group 3
for
RECLOSURE SHOT 2
,
Group 4
for
RECLOSURE SHOT 3
, and
Group 1
for
RECLOSURE SHOT 4
.
3.
Set the test set to a current level above the pickup of these elements. With the current source off, Reset
the relay, and clear the event recorder.
4.
Turn on the current. The relay should Trip + AR 4 times caused by the following elements, in order, Phase
Time OC 1, Phase Time OC 2, Phase Inst OC 1, Phase Inst OC 2, Phase Time OC 1. The event recorder
will show this sequence of events. Turn off the current, and reset the relay.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...