16-
20
750/760 Feeder Management Relay
GE Power Management
16.4 MODBUS MEMORY MAP
16 COMMUNICATIONS
16
0271
8
Reclosure Count Last Reset Date (2 words)
---
---
F23
---
A1
LAST TRIP DATA
READ ONLY
02E0
Date of Last Trip (2 words)
---
---
F23
---
02E2
Time of Last Trip (2 words)
---
---
F22
---
02E4
Cause of Last Trip
---
---
F24
---
02E5
Last Trip Phase A Current
0 to 65535
A
F1
---
02E6
Last Trip Phase B Current
0 to 65535
A
F1
---
02E7
Last Trip Phase C Current
0 to 65535
A
F1
---
02E8
Last Trip Ground Current
0 to 65535
A
F1
---
02E9
Last Trip A-N (A-B) Voltage
0.00 to 600.00
kV
F3
---
02EA
Last Trip B-N (B-C) Voltage
0.00 to 600.00
kV
F3
---
02EB
Last Trip C-N (C-A) Voltage
0.00 to 600.00
kV
F3
---
02EC
Last Trip System Frequency
0.00 to 90.00
Hz
F3
---
02ED
Last Trip Analog Input
0 to 65535
Units
F1
---
02EE
Last Trip Neutral Current
0 to 65535
A
F1
---
02EF
3
Last Trip Sensitive Ground Current
0.00 to 655.35
A
F3
---
02F0
5
Last Trip Neutral Voltage
0.00 to 655.35
kV
F3
---
A2
CURRENT AND VOLTAGE
READ ONLY
02FE
5
Neutral Voltage
0.00 to 655.35
kV
F3
---
02FF
3
Sensitive Ground Current
0.00 to 655.35
A
F3
---
0300
Phase A RMS Current
0 to 65535
A
F1
---
0301
Phase B RMS Current
0 to 65535
A
F1
---
0302
Phase C RMS Current
0 to 65535
A
F1
---
0303
Percent of Load-to-Trip
0 to 2000
%
F1
---
0304
Ground Current
0 to 65535
A
F1
---
0305
A-N RMS Voltage
0.00 to 600.00
kV
F3
---
0306
B-N RMS Voltage
0.00 to 600.00
kV
F3
---
0307
C-N RMS Voltage
0.00 to 600.00
kV
F3
---
0308
A-B RMS Voltage
0.00 to 600.00
kV
F3
---
0309
B-C RMS Voltage
0.00 to 600.00
kV
F3
---
030A
C-A RMS Voltage
0.00 to 600.00
kV
F3
---
030B
3
Reserved for Polarizing Current
---
---
---
---
030C
Average Current
0 to 65535
A
F1
---
030D
Average Line Voltage
0.00 to 600.00
kV
F3
---
030E
Average Phase Voltage
0.00 to 600.00
kV
F3
---
030F
Neutral Current
0 to 65535
A
F1
---
Table 16–15: MODBUS MEMORY MAP (Sheet 3 of 41)
ADDR
DESCRIPTION
RANGE
UNITS
TYPE
FACTORY
DEFAULT
1 2 3 4 5 6 7 8 9
For explanation of Table footnotes, see page 16–59.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...