GE Power Management
750/760 Feeder Management Relay
16-
39
16 COMMUNICATIONS
16.4 MODBUS MEMORY MAP
16
146A
FlexCurve A Trip Time at 9.50 x PU
0 to 65535
ms
F1
0 ms
146B
FlexCurve A Trip Time at 10.0 x PU
0 to 65535
ms
F1
0 ms
146C
FlexCurve A Trip Time at 10.5 x PU
0 to 65535
ms
F1
0 ms
146D
FlexCurve A Trip Time at 11.0 x PU
0 to 65535
ms
F1
0 ms
146E
FlexCurve A Trip Time at 11.5 x PU
0 to 65535
ms
F1
0 ms
146F
FlexCurve A Trip Time at 12.0 x PU
0 to 65535
ms
F1
0 ms
1470
FlexCurve A Trip Time at 12.5 x PU
0 to 65535
ms
F1
0 ms
1471
FlexCurve A Trip Time at 13.0 x PU
0 to 65535
ms
F1
0 ms
1472
FlexCurve A Trip Time at 13.5 x PU
0 to 65535
ms
F1
0 ms
1473
FlexCurve A Trip Time at 14.0 x PU
0 to 65535
ms
F1
0 ms
1474
FlexCurve A Trip Time at 14.5 x PU
0 to 65535
ms
F1
0 ms
1475
FlexCurve A Trip Time at 15.0 x PU
0 to 65535
ms
F1
0 ms
1476
FlexCurve A Trip Time at 15.5 x PU
0 to 65535
ms
F1
0 ms
1477
FlexCurve A Trip Time at 16.0 x PU
0 to 65535
ms
F1
0 ms
1478
FlexCurve A Trip Time at 16.5 x PU
0 to 65535
ms
F1
0 ms
1479
FlexCurve A Trip Time at 17.0 x PU
0 to 65535
ms
F1
0 ms
147A
FlexCurve A Trip Time at 17.5 x PU
0 to 65535
ms
F1
0 ms
147B
FlexCurve A Trip Time at 18.0 x PU
0 to 65535
ms
F1
0 ms
147C
FlexCurve A Trip Time at 18.5 x PU
0 to 65535
ms
F1
0 ms
147D
FlexCurve A Trip Time at 19.0 x PU
0 to 65535
ms
F1
0 ms
147E
FlexCurve A Trip Time at 19.5 x PU
0 to 65535
ms
F1
0 ms
147F
FlexCurve A Trip Time at 20.0 x PU
0 to 65535
ms
F1
0 ms
S2
FLEXCURVE B
READ/WRITE
1480
FlexCurve B (80 words - see FlexCurve A)
0 to 65535
ms
F1
0 ms
S5
PHASE TIME OVERCURRENT 1
READ/WRITE
1500
Phase Time Overcurrent 1 Function
---
---
F37
Trip
1501
Phase Time Overcurrent 1 Relays
---
---
F57
None
1502
2
Phase Time Overcurrent 1 Curve
---
---
F36
Ext Inverse
1503
Phase Time Overcurrent 1 Voltage Restraint
---
---
F30
Disabled
1504
1
Phase Time Overcurrent 1 Pickup
0.05 to 20.00
x CT
F3
1.00 x CT
1505
1
Phase Time Overcurrent 1 Multiplier
0.00 to 100.00
---
F3
1.00
1506
1
Phase Time Overcurrent 1 Reset Time
---
---
F68
Instantaneous
1507
1
Phase Time Overcurrent 1 Direction
---
---
F84
Disabled
S5
PHASE INSTANTANEOUS OVERCURRENT 1
READ/WRITE
1508
2
Phase Instantaneous Overcurrent 1 Function
---
---
F37
Disabled
1509
2
Phase Instantaneous Overcurrent 1 Relays
---
---
F57
None
Table 16–15: MODBUS MEMORY MAP (Sheet 22 of 41)
ADDR
DESCRIPTION
RANGE
UNITS
TYPE
FACTORY
DEFAULT
1 2 3 4 5 6 7 8 9
For explanation of Table footnotes, see page 16–59.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...