750/760 Feeder Management Relay
GE Power Management
5.4 MESSAGES
5 FRONT PANEL OPERATION
5
Table 5–1: SELF-TEST WARNINGS
ERROR
SEVERITY
DESCRIPTION
A/D Virtual Ground
Major
This warning is caused by a failure of the analog to digital converter. The
integrity of system input measurements is affected by this failure.
Analog 32V
Minor
Caused by the loss of the +32 V DC power supply used to power analog
outputs. Analog output currents are affected by this failure.
Clock Not Set
Minor
Occurs if the clock has not been set.
Dry C32V
Minor
Caused by the loss of the +32 V DC power supply used to power dry
contacts of logic inputs. Logic inputs using internal power are affected
by this failure.
EEPROM Corrupt
Major
This warning is caused by detection of corrupted location(s) in the relay
data memory which cannot be self-corrected. Any function of the relay is
susceptible to malfunction from this failure.
Factory Service
Major
This warning occurs when the relay is in factory service mode.
FLASH Corrupt
Major
This warning is caused by detection of a corrupted location in the
program memory as determined by a CRC error checking code. Any
function of the relay is susceptible to malfunction from this failure.
Force Analog Out
Minor
Occurs when the setpoint
FORCE ANALOG OUTPUTS FUNCTION
is set to
Enabled.
Force Relays
Minor
Occurs when the setpoint
FORCE OUTPUT RELAYS FUNCTION
is set to
Enabled.
Internal RS485
Minor
Caused by a failure of the internal RS485 communication link. Attempts
to read Actual Values or write Setpoints will produce unpredictable
results.
Internal Temp
Minor
Caused by the detection of unacceptably low (less than –40
°
C) or high
(greater than +85
°
C) temperatures detected inside the unit.
IRIG-B Failure
Minor
This warning is caused when IRIG-B time synchronization has been
enabled but the signal cannot be decoded.
Not Calibrated
Minor
This warning occurs when the relay has not been factory calibrated.
Pickup Test
Minor
Occurs when the setpoint
PICKUP TEST FUNCTION
is set to Enabled.
Prototype Software
Minor
Occurs when prototype software has been loaded into the relay.
Relay Not Ready
Minor
This warning occurs when the installation setpoint
750/760 OPERATION
has not been set to Ready.
RTC Crystal
Minor
This warning is caused by a failure of the Real Time Clock circuit. The
ability of the relay to maintain the current date and time is lost.
Simulation Mode
Minor
This warning occurs when the simulation feature of the relay is active.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...