GE Power Management
750/760 Feeder Management Relay
2-
7
2 GETTING STARTED
2.3 SAMPLE APPLICATION
2
PHASE TIME OC 1 CURVE:
Mod Inverse
PHASE TIME OC 1 MULTIPLIER:
20.20
PHASE TIME OC 1 RESET:
Instantaneous
b) PHASE INSTANTANEOUS O/C 1
S5 PROTECTION \ PHASE CURRENT \ PHASE INST OC 1 \
PHASE INST OC 1 FUNCTION:
Trip
PHASE INST OC 1 PICKUP:
1.40 x CT
(840A pickup / 600A CT pri)
PHASE INST OC 1 DELAY:
0.00 s
PHASES REQUIRED FOR OPERATION:
Any Two
c) PHASE INSTANTANEOUS O/C 2
S5 PROTECTION \ PHASE CURRENT \ PHASE INST OC 2 \
PHASE INST OC 2 FUNCTION:
Trip
PHASE INST OC 2 PICKUP:
16.83 x CT
(10100A pickup / 600 A pri)
PHASE INST OC 2 DELAY:
0.00 s
PHASES REQUIRED FOR OPERATION:
Any Two
d) NEUTRAL TIME O/C 1
S5 PROTECTION \ NEUTRAL CURRENT \ NEUTRAL TIME OC 1 \
NEUTRAL TIME OC 1 FUNCTION:
Trip
NEUTRAL TIME OC 1 PICKUP:
0.20 x CT
(120A pickup / 600A pri)
NEUTRAL TIME OC 1 CURVE:
Mod Inverse
NEUTRAL TIME OC 1 MULTIPLIER:
10.00
NEUTRAL TIME OC 1 RESET:
Instantaneous
e) NEUTRAL INSTANTANEOUS O/C 1
S5 PROTECTION \ NEUTRAL CURRENT \ NEUTRAL INST OC 1 \
NEUTRAL INST OC 1 FUNCTION:
Trip
NEUTRAL INST OC 1 PICKUP:
0.20 x CT
(120A pickup / 600A pri)
NEUTRAL INST OC 1 DELAY:
0.00 s
f) NEUTRAL INSTANTANEOUS O/C 2
S5 PROTECTION \ NEUTRAL CURRENT \ NEUTRAL INST OC 2 \
NEUTRAL INST OC 2 FUNCTION:
Trip
NEUTRAL INST OC 2 PICKUP:
3.33 x CT
(2000A pickup / 600A pri)
NEUTRAL INST OC 2 DELAY:
0.00 s
g) GROUND TIME OVERCURRENT
S5 PROTECTION \ GROUND CURRENT \ GROUND TIME OC \ GROUND TIME O/C FUNCTION:
Disabled
h) GROUND INSTANTANEOUS OVERCURRENT
S5 PROTECTION \ GROUND CURRENT \ GROUND INST OC \ GROUND INST O/C FUNCTION:
Disabled
i) NEGATIVE SEQUENCE TIME OVERCURRENT
S5 PROTECTION \ NEGATIVE SEQUENCE \ NEG SEQ TIME OC \ NEG SEQ TIME OC FUNCTION:
Disabled
j) NEGATIVE SEQUENCE INSTANTANEOUS OVERCURRENT
S5 PROTECTION \ NEGATIVE SEQUENCE \ NEG SEQ INST OC \ NEG SEQ INST O/C FUNCTION:
Disabled
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...