GE Power Management
750/760 Feeder Management Relay
13-
25
13 S6 MONITORING
13.6 ANALOG OUTPUTS
13
13.6.2 ANALOG OUTPUT PARAMETER SELECTIONS
Table 13–1: ANALOG OUTPUT PARAMETER SELECTIONS (Sheet 1 of 2)
PARAMETER NAME
RANGE / UNITS
STEP
DEFAULTS
CHANNEL
TYPE
MIN.
MAX.
Phase A/B/C Current
0 to 65535 Amps
1
0
2000
A
Phase A/B/C Current Angle
0 to 359
°
Lag
1
0
359
A
Average Current
0 to 65535 Amps
1
0
2000
A
% Of Load-To-Trip
0 to 2000%
1
0
1000
A
Neutral Current
0 to 65535 Amps
1
0
2000
A
Neutral Current Angle
0 to 359
°
Lag
1
0
359
A
Phase AN/BN/CN Voltage
0.00 to 655.35 kV
0.01
0.00
100.00
A
Phase AN/BN/CN Voltage Angle
0 to 359
°
Lag
1
0
359
A
Average Phase Voltage
0.00 to 655.35 kV
0.01
0.00
100.00
A
Line AB/BC/CA Voltage
0.00 to 655.35 kV
0.01
0.00
100.00
A
Line AB/BC/CA Voltage Angle
0 to 359
°
Lag
1
0
359
A
Average Line Voltage
0.00 to 655.35 kV
0.01
0.00
100.00
A
Frequency
20.00 to 65.00 Hz
0.01
47.00
63.00
B
3
φ
Real Power
–3000.0 to 3000.0 MW
1
0.1
–100.0
100.0
C
3
φ
Reactive Power
–3000.0 to 3000.0 Mvar
1
0.1
–100.0
100.0
C
3
φ
Apparent Power
0.0 to 3000.0 MVA
1
0.1
0.0
100.0
A
3
φ
Power Factor
0.00 Lead to 0.00 Lag
0.01
0.99 Lag
0.50 Lag
B
Last Phase A/B/C Demand
0 to 65535 Amps
1
0
2000
A
Last Watt Demand
–3000.0 to 3000.0 MW
1
0.1
–100.0
100.0
C
Last Var Demand
–3000.0 to 3000.0 Mvar
1
0.1
–100.0
100.0
C
Last VA Demand
0.0 to 3000.0 MVA
1
0.1
0.0
100.0
A
Analog Input
0 to 65535 Units
1
0
1000
A
Last Fault Distance
–327.67 to 327.67 km/miles
0.01
–50.00
50.00
C
Positive Watthours
0.0 to 6553.5 MWh
1
0.1
0.0
1000.0
A
Negative Watthours
0.0 to 6553.5 MWh
1
0.1
0.0
1000.0
A
Positive Varhours
0.0 to 6553.5 Mvarh
1
0.1
0.0
1000.0
A
Negative Varhours
0.0 to 6553.5 Mvarh
1
0.1
0.0
1000.0
A
Ground Current
0 to 65535 Amps
1
0
2000
A
Ground Current Angle
0 to 359
°
Lag
1
0
359
A
Polarizing Current
0 to 65535 Amps
1
0
2000
A
Polarizing Current Angle
0 to 359
°
Lag
1
0
359
A
φ
A/
φ
B/
φ
C Real Power
–3000.0 to 3000.0 MW
1
0.1
–100.0
100.0
C
φ
A/
φ
B/
φ
C Reactive Power
–3000.0 to 3000.0 Mvar
1
0.1
–100.0
100.0
C
1
Power and energy quantities auto-range to display units appropriate to power system size.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...