13 S6 MONITORING
13.1 CURRENT LEVEL
13
13 S6 MONITORING 13.1 CURRENT LEVEL
13.1.1 DESCRIPTION
In addition to the conventional overcurrent protection elements that are used for tripping, separate phase and
neutral current level detectors are provided for alarm or control purposes. These elements allow longer time
delays to be programmed.
13.1.2 PHASE CURRENT LEVEL
13.1.3 NEUTRAL CURRENT LEVEL
■
PHASE CURRENT
■
[ENTER] for more
The
PHASE CURRENT
Level setpoints path is:
\ SETPOINTS \ S6 MONITORING \ CURRENT LEVEL \ PHASE CURRENT
PHASE CURRENT
FUNCTION: Disabled
Range: Disabled, Alarm, Latched Alarm, Control
Select the required function.
PHASE CURRENT
RELAYS (3-7): -----
Range: Any Combination of the 3-7 AUXILIARY Relays
Select the output relays required.
PHASE CURRENT
PICKUP: 1.00 x CT
Range: 0.05 to 20.00 in steps of 0.01 x CT
Enter the pickup in terms of the CT rating. If 100:5 phase CTs are installed,
enter
0.9 x CT
for an alarm level of 90 amps.
PHASE CURRENT
DELAY:
2 s
Range: 0 to 60000 in steps of 1 s
Select the delay required.
■
NEUTRAL CURRENT
■
[ENTER] for more
The
NEUTRAL CURRENT
Level setpoints path is:
\ SETPOINTS \ S6 MONITORING \ CURRENT LEVEL \ NEUTRAL CURRENT
NEUTRAL CURRENT
FUNCTION: Disabled
Range: Disabled, Alarm, Control
Select the function required.
NEUTRAL CURRENT
RELAYS (3-7): -----
Range: Any Combination of the 3-7 AUXILIARY Relays
Select the output relays required.
NEUTRAL CURRENT
PICKUP: 1.10 x CT
Range: 0.05 to 20.00 in steps of 0.01 x CT
Enter the pickup in terms of the CT rating. If 100:5 phase CTs are installed,
enter
0.9 x CT
for an alarm level of 90 amps.
NEUTRAL CURRENT
DELAY:
2 s
Range: 0 to 60000 in steps of 1 s
Select the delay required.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...