750/760 Feeder Management Relay
GE Power Management
1.2 TECHNICAL SPECIFICATIONS
1 PRODUCT OVERVIEW
1
GROUND / SENSITIVE GROUND DIRECTIONAL
CONTROL
Polarized by voltage, current or both voltage and current
(For voltage element polarizing, the source VTs must be
connected in Wye).
Polarizing Voltage:
-Vo
Polarizing Current:
Ig
MTA:
0 to 359° in steps of 1°
Angle Accuracy:
± 2°
Operation Delay:
25 to 40 ms
BUS UNDERVOLTAGE 1 / 2 AND LINE UNDER-
VOLTAGE 3 / 4
Minimum Voltage:
> programmable threshold from
0.00 to 1.25 x VT in steps of 0.01
Pickup Level:
0.00 to 1.25 in steps of 0.01 x VT
Dropout Level:
102 to 103% of Pickup
Curve:
definite time or inverse time
Time Delay:
0.0 to 6000.0 in steps of 0.1 s
Phases:
Any One/Any Two/All Three (pro-
grammed) to operate for output (bus
undervoltage only)
Level Accuracy:
Per voltage input
Timing Accuracy:
± 100 ms
OVERVOLTAGE 1 / 2
Pickup Level:
0.00 to 1.25 in steps of 0.01 x VT
Dropout Level:
97 to 98% of Pickup
Time Delay:
0.0 to 6000.0 in steps of 0.1 s (defi-
nite time)
Phases:
Any One/Any Two/All Three (pro-
grammable) phases have to operate
for output
Level Accuracy:
Per voltage input
Timing Accuracy:
± 100 ms
NEGATIVE SEQUENCE VOLTAGE
Pickup Level:
0.00 to 1.25 in steps of 0.01 x VT
Dropout Level:
97 to 98% of Pickup
Time Delay:
0.0 to 6000.0 in steps of 0.1 (definite
or inverse time)
Level Accuracy:
3 x voltage input error
Timing Accuracy:
± 100 ms
UNDERFREQUENCY 1 / 2
Minimum Voltage:
0.00 to 1.25 in steps of 0.01 x VT in
Phase A
Pickup Level:
20.00 to 65.00 in steps of 0.01 Hz
Dropout Level:
0.03 Hz
Time Delay:
0.00 to 600.00 in steps of 0.01 s
(definite time)
Level Accuracy:
± 0.02 Hz
Timing Accuracy:
at 60 Hz: ± 25 ms
at 50 Hz: ± 30 ms
BREAKER FAILURE
Pickup Level:
0.05 to 20.0 x CT in steps of 0.01
Dropout Level:
97 to 98% of Pickup
Time Delay:
0.03 to 1.00 s in steps of 10
Timing Accuracy:
± 20 ms error
Level Accuracy:
per CT input
NEUTRAL DISPLACEMENT
Pickup Level:
0.00 to 1.25 in steps of 0.01 x VT
Dropout Level:
97 to 98% of Pickup
Curve Shape:
ANSI Extremely/Very/Moderately/
Normally Inverse
Definite Time (0.1 s base curve)
IEC Curve A/B/C and Short
FlexCurve™ A/B (programmable
curves)
IAC Extreme/Very/Inverse/Short
Curve Multiplier:
0.00 to 100.00 in steps of 0.01
Reset Type:
Instantaneous/Linear
Level Accuracy:
3 x voltage input error
Timing Accuracy:
±50 ms
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...