GE Power Management
750/760 Feeder Management Relay
17-
71
17 COMMISSIONING
17.9 CONTROL SCHEMES
17
For all further testing, ensure that a reclose is not initiated until after the programmed ‘AR
block time upon manual close’ has elapsed, after a manual close.
5.
Assert a Block Reclosure logic input. The RECLOSURE ENABLED indicator should go out and the
RECLOSURE DISABLED indicator come on. De-assert the Block Reclosure logic input. The RECLO-
SURE ENABLED indicator should come on and the RECLOSURE DISABLED indicator should go out.
6.
Assert a Cancel Reclosure logic input. The RECLOSURE ENABLED indicator should go out and the
RECLOSURE DISABLED indicator come on. De-assert the Cancel Reclosure logic input. The RECLO-
SURE ENABLED indicator should come on and the RECLOSURE DISABLED indicator should go out.
7.
Display
A1 STATUS \ AUTORECLOSE \ AUTORECLOSE SHOT IN EFFECT
– the value displayed should be
0
.
8.
Momentarily assert the Initiate Reclosure logic input. The RECLOSURE IN PROGRESS indicator should
come on immediately, and any output relays programmed to operate for Reclose In Progress should now
be operated. After the delay programmed for Incompleted Sequence Time the RECLOSURE IN
PROGRESS indicator will go out, as the breaker has not tripped, and the incomplete sequence timer has
canceled the reclose in progress. Any output relays operated above should now be reset. Check the inter-
val of the incomplete sequence timer by observing the RECLOSURE IN PROGRESS LED.
9.
Momentarily assert the Initiate Reclosure logic input causing a reclose in progress indication. Immediately
assert the Block Reclosure logic input and the scheme should become disabled, canceling the reclose in
progress. Assert the Initiate Reclosure logic input and check that the scheme does not become in
progress. De-assert the Block Reclosure logic input and the scheme should become in progress.
10. Assert a Cancel Reclosure logic input and the scheme should become disabled, canceling the reclose in
progress. De-assert the Cancel Reclosure logic input and the scheme should become enabled.
11. Assert the Initiate Reclosure logic input then immediately after assert the Remote Open logic input, initiat-
ing a reclose and tripping the breaker. (The RECLOSURE IN PROGRESS indicator is now on.) Check that
AUTORECLOSE SHOT IN EFFECT
is 0. Before the programmed dead-time interval for Reclosure 1 has elapsed,
press the BREAKER CLOSE pushbutton. The breaker should not close, as reclose is in progress. The
breaker should reclose at the end of the dead-time interval, incrementing the shot counter to 1. Before the
scheme resets check that the reading under
A1 STATUS \ AUTORECLOSE \ AUTORECLOSE SHOTS REMAINING
is
the number of shots programmed less one. This reading should change to the number of shots pro-
grammed when the scheme is automatically reset at the end of the reset interval. The event recorder
should have recorded logic input Initiate Reclosure, Remote Open, the Reclose, and Reclosure Reset.
Check the interval of the autoreclose reset timer in the event recorder.
12. Assert the Initiate Reclosure logic input then immediately after assert the Remote Open logic input, initiat-
ing a reclose and tripping the breaker. Check that the breaker trips and later recloses, and the displayed
number of shots remaining is reduced by one. Immediately assert the Initiate Reclosure and Remote Open
logic inputs again, to initiate another trip and reclose and the displayed number of shots remaining is
reduced by one again. Repeat this procedure until the programmed number of shots have been per-
formed. Initiate Reclosure once more and the scheme should go to lockout; the RECLOSURE LOCKOUT
and RECLOSE DISABLED indicators should now be on, and the RECLOSURE ENABLED indicator
should be off. Any output relays programmed to operate for Lockout should now be operated.
13. The event recorder should have recorded each logic input for Initiate Reclosure, each Reclose, and Reclo-
sure Lockout. Check the interval of deadtime for each shot in the event recorder.
14. Press the relay RESET pushbutton; Lockout should be canceled and the displayed number of shots
should return to the programmed value. (The event recorder should record this reset.) Check that the
RECLOSE LOCKOUT and RECLOSE DISABLED indicators are off, and the RECLOSURE ENABLED
indicator is now on. Any output relays operated above should now be de-energized. Close the breaker.
15. Repeat step 12. Assert a Close command, either locally or remotely, and observe that lockout is reset at
the end of the AR block time upon manual close, with indications as above.
NOTE
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...