17 COMMISSIONING
17.9 CONTROL SCHEMES
17
17.9 CONTROL SCHEMES
17.9.1 SETPOINT GROUP CONTROL
The relay is defaulted to setpoint group 1, and will be using this group for setpoints unless
specifically changed to another group. This procedure assumes the relay is using group 1 ini-
tially, as indicated by the LED on the faceplate.
Make connections per Figure 17–1: RELAY TEST WIRING – WYE CONNECTION or Figure 17–2: RELAY
TEST WIRING – DELTA CONNECTION on page 17–4.
1.
Change setpoint
SETPOINTS \ S7 CONTROL \ SETPOINT GROUPS \ ACTIVE SETPOINT GROUP
to Group 2 with the
EDIT SETPOINT GROUP
set to Active Group. The LED on the faceplate should now indicate the relay is using
setpoint group 2.
2.
Change at least one protection element setpoint from the setting in group 1.
3.
Repeat steps 2 and 3 for active setpoint group selections of Group 3 and Group 4, while monitoring that
the LED indicators show the correct group.
4.
Check that the operation of the protection feature programmed is controlled by the setting in group 4.
5.
Change setpoint
SETPOINTS \ S7 CONTROL \ SETPOINT GROUPS \ ACTIVE SETPOINT GROUP
to Group 3. The LED
on the faceplate should now indicate the relay is using setpoint group 3.
6.
Check that the operation of the protection feature programmed is controlled by the setting in group 3.
7.
Change setpoint
SETPOINTS \ S7 CONTROL \ SETPOINT GROUPS \ ACTIVE SETPOINT GROUP
to Group 2. The LED
on the faceplate should now indicate the relay is using setpoint group 2.
8.
Check that the operation of the protection feature programmed is controlled by the setting in group 2.
9.
Change setpoint
SETPOINTS \ S7 CONTROL \ SETPOINT GROUPS \ ACTIVE SETPOINT GROUP
to Group 1. The LED
on the faceplate should now indicate the relay is using setpoint group 1.
10. Check that the operation of the protection feature programmed is controlled by the setting in group 1.
11. Assert logic input Setpoint Group 2, and check that the LED indicator shows Setpoint Group 2.
12. Assert logic input Setpoint Group 3, and check that the LED indicator shows Setpoint Group 3.
13. Assert logic input Setpoint Group 4, and check that the LED indicator shows Setpoint Group 4.
14. De-assert logic input Setpoint Group 4, and check that the LED indicator shows Setpoint Group 3.
15. De-assert logic input Setpoint Group 3, and check that the LED indicator shows Setpoint Group 2.
16. De-assert logic input Setpoint Group 2, and check that the LED indicator shows Setpoint Group 1.
17. Check that the changing of setpoint groups is placed in the event recorder.
If setpoint BREAKER OPEN INHIBIT is to be Enabled
1.
Assert a breaker state logic input so that the relay determines the breaker is closed.
2.
Assert logic input Setpoint Group 2. The faceplate LED should indicate the relay is using setpoint group 2.
3.
De-assert the breaker state logic input so that the relay determines the breaker is open.
4.
De-assert logic input Setpoint Group 2. The LED on the faceplate should indicate the relay is still using set-
point group 2.
5.
Assert the breaker state logic input so that the relay determines the breaker is closed.
6.
The LED on the faceplate should indicate the relay is now using setpoint group 1.
NOTE
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...