GE Power Management
750/760 Feeder Management Relay
1-
7
1 PRODUCT OVERVIEW
1.2 TECHNICAL SPECIFICATIONS
1
1.2 TECHNICAL SPECIFICATIONS
1.2.1 APPLICABILITY
Systems:
3 or 4 wire, 600 kV maximum, 5000 Amp maximum
Frequency:
25 to 60 Hz nominal (frequency tracking allows operation from 16-65 Hz)
1.2.2 INPUTS
CONTROL POWER
Options:
LO/HI (specified when ordering)
LO Range:
DC = 20 to 60 V
AC = 20 to 48 V @ 48 to 62 Hz.
HI Range:
DC = 88 to 300 V
AC = 70 to 265 V @ 48 to 62 Hz.
Power:
25 VA nominal, 35 VA maximum
Voltage Loss Hold-Up Time:30 ms
PHASE CURRENT INPUT
Source CT:
1 to 50000 A primary,
1 or 5 A secondary
Relay Input:
1 A or 5 A (specified when ordering)
Burden:
Less than 0.2 VA at 1 or 5 A
Conversion Range:
0.01 to 20 x CT
(fundamental frequency only)
Accuracy:
at < 2 x CT: ± 0.5% of 2 x CT
at
≥
2 x CT: ± 1% of 20 x CT
Overload Withstand:
1 second @ 80 times rated current
continuous @ 3 times rated current
Calculated Neutral Current Errors:3 x phase inputs
GROUND CURRENT INPUT
Source CT:
1 to 50000 A primary,
1 or 5 A secondary
Relay Input:
1 A or 5 A (specified when ordering)
Burden:
Less than 0.2 VA at 1 or 5 A
Conversion Range:
0.01 to 20 x CT
(fundamental frequency only)
Accuracy:
at < 2 x CT: ± 0.5% of 2 x CT
at
≥
2 x CT: ± 1% of 20 x CT
Overload Withstand:
1 second @ 80 times rated current
continuous @ 3 times rated current
SENSITIVE GROUND CURRENT INPUT
Source CT:
1 to 50000 A primary,
1 or 5 A secondary
Relay Input:
1 A or 5 A (specified when ordering)
Burden:
Less than 0.2 VA at 1 or 5 A
Conversion Range:
Low End:
0.005 x CT
Maximum:
500 A primary
(fundamental frequency only)
Accuracy:
at < 0.1 x CT: ± 0.2% of 1 x CT
at
≥
0.1 x CT: ± 1% of 1 x CT
Overload Withstand:
1 second @ 80 times rated current
continuous @ 3 times rated current
BUS AND LINE VOLTAGE INPUTS
Source VT:
0.12 to 600 kV / 50 to 240 V
Source VT Ratio:
1 to 5000 in steps of 0.1
Relay Input:
50 V to 240 V phase-neutral
Burden:
Less than 0.025 VA at 120 V
or > 576 K
Ω
Max. Continuous:
273 V phase-neutral (Full Scale) CT
(fundamental frequency only)
Accuracy (0°-40°C):
± 0.25% of full scale (10 to 130 V);
± 0.8% of full scale (130 to 273 V)
(for open delta, the calculated
phase has errors 2 times those
shown above)
LOGIC INPUTS
Inputs:
14 contact and / or virtual,
6 virtual only (Functions assigned to
logic inputs)
Dry Contacts:
1000
Ω
maximum ON resistance
(32 V DC @ 2 mA provided by relay)
Wet Contacts:
30 to 300 V DC @ 2.0 mA
(External DC voltage only)
ANALOG INPUT
Current Input:
0-1 mA, 0-5 mA, 0-10 mA, 0-20 mA,
or 4-20 mA (programmable)
Input Impedance:
375
Ω
± 10%
Conversion Range:
0 to 21 mA
Accuracy:
± 1% of full scale
TRIP AND CLOSE COIL MONITORING INPUTS
Acceptable Voltage
Range:
20 to 250 V DC
Trickle Current:
2 mA to 5 mA
IRIG-B INPUT
Amplitude-Modulated: 2.5 to 6 Vp-p @ 3:1 signal ratio
DC Shift:
TTL
Input Impedance:
20 k
Ω
±10%
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...