8 S1 RELAY SETUP
8.8 FRONT PANEL
8
8.8 FRONT PANEL
8.8.1 DESCRIPTION
Some of the front panel relay characteristics can be modified to suit different situations.
8.8.2 SETTINGS
Firmware versions 3.70 and greater do not support a keypad beeper as did previous firmware
versions. The PC software does not support keypad beeper operation.
■
FRONT PANEL
■
[ENTER] for more
The Front Panel setpoints path is:
\ SETPOINTS \ S1 RELAY SETUP \ FRONT PANEL
FLASH MESSAGE TIME:
4.0 s
Range: 0.5 to 10.0 in steps of 0.1 s
Flash messages are status, warning, error, or information messages displayed
for several seconds in response to certain key presses during setpoint pro-
gramming. The time these messages remain on the display, overriding the nor-
mal messages, can be changed to accommodate different user reading rates.
DEFAULT MESSAGE
TIME: 300 s
Range: 10 to 900 in steps of 1 s
If no keys are pressed for a period of time, the relay will automatically begin to
display a programmed set of default messages. This time can be modified to
ensure menu messages remain on the screen long enough during program-
ming or reading of actual values. Once default scanning starts, pressing any
key will restore the last message displayed on the screen.
DEFAULT MESSAGE
INTENSITY: 25 %
Range: 25 to 100 in steps of 25%
To extend the life of the phosphor in the vacuum fluorescent display, the bright-
ness of the display can be attenuated when default messages are being dis-
played. When interacting with the display using the front panel keys, the
display will always operate at full brightness.
DISPLAY FILTER
CONSTANT:
0
Range: 0 to 255 in steps of 1
This value is used for filtering the displayed values of current, voltage, and
power. It determines how quickly the filter responds and how much the filter
will ‘smooth’ the display values. Smaller values result in quicker response
times, but with less smoothing. Larger values result in a slower response time,
but with more smoothing. A value of
0
completely disables the filter. A value of
224
results in a reasonably smooth display value with a response time of about
one second. A value of
255
results in a very smooth display value, but with a
response time of about five seconds.
3 KEY MAX DEMAND
CLEARING: Disabled
Range: Disabled, Enabled.
For increased ease of Max Demand clearing, this setpoint enables the use of
the key sequence
,
,
to force the max demand values to
clear. This key sequence operates on any setpoint or actual values page. The
keystrokes must be entered in the above order. Any other variation of the key
sequence will not permit the clearing of the Max Demand Values.
NOTE
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...