12.5 SENSITIVE GROUND CURRENT
12 S5 PROTECTION
12
12.5 SENSITIVE GROUND CURRENT
12.5.1 DESCRIPTION
Two sensitive ground overcurrent protection elements are provided. One time overcurrent element and one
instantaneous element. Sensitive ground overcurrent elements can be controlled by the sensitive ground direc-
tional element allowing operation for faults in the permitted direction only. Also, the elements can be blocked
individually or as a group by logic inputs.
12.5.2 SENSITIVE GROUND TIME OVERCURRENT
The sensitive ground time overcurrent element, ANSI device 51SG is programmed in this subgroup.
■
SENSTV GND TIME OC
■
[ENTER] for more
The Sensitive Ground Time Overcurrent setpoints path is:
\ SETPOINTS \ S5 PROTECTION \ SENSTV GND CURRENT \ SENSTV GND TIME OC
SENSTV GND TIME OC
FUNCTION: Disabled
Range: Disabled, Trip, Trip & AR, Alarm, Latched Alarm, Control
Select the required function.
SENSTV GND TIME OC
RELAYS (3-7): -----
Range: Any Combination of the 3-7 AUXILIARY Relays
Select the output relays required.
SENSTV GND TIME OC
PICKUP: 1.00 x CT
Range: 0.005 to 1.000 in steps of 0.001 x CT
Select the sensitive ground current level required for pickup.
SENSTV GND TIME OC
CURVE: Ext Inverse
Range: Ext Inverse, Very Inverse, Norm Inverse, ..., Flex Curve B
See description in Section 12.1: TIME OVERCURRENT CURVE CHARAC-
TERISTICS on page 12–1.
SENSTV GND TIME OC
MULTIPLIER:
1.00
Range: 0.00 to 100.00 in steps of 0.01
See description in Section 12.1: TIME OVERCURRENT CURVE CHARAC-
TERISTICS on page 12–1.
SENSTV GND TIME OC
RESET: Instantaneous
Range: Instantaneous, Linear
See description in Section 12.1: TIME OVERCURRENT CURVE CHARAC-
TERISTICS on page 12–1.
SENSTV GND TIME OC
DIRECTION: Disabled
Range: Disabled, Forward, Reverse
Select the direction(s) of current flow for which operation is permitted.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...