12 S5 PROTECTION
12.5 SENSITIVE GROUND CURRENT
12
12.5.5 SENSITIVE GROUND DIRECTIONAL SETPOINTS
■
SENSTV GND DIRECTN
■
[ENTER] for more
The Sensitive Ground Directional setpoints path is:
\ SETPOINTS \ S5 PROTECTION \ SENSTV GND CURRENT \ SENSTV GND DIRECTN
SENSTV GND DIRECTN
FUNCTION: Disabled
Range: Disabled, Alarm, Latched Alarm, Control
Select the required function.
SENSTV GND DIRECTN
RELAYS (3-7): -----
Range: Any Combination of the 3-7 AUXILIARY Relays
Select the output relays required.
SENS GND POLARIZING:
Voltage
Range: Voltage, Current, Dual
If sensitive ground directional control with both voltage and current polarized
elements is desired, enter
Dual
. With this setting, both polarizing quantities
must agree that the operating current is in the reverse direction for the sensi-
tive ground directional element to operate the selected output relays. If sensi-
tive ground directional control with only the voltage polarized element is
desired, enter
Voltage
. If sensitive ground directional control with only the cur-
rent polarized element is desired, enter
Current
.
SENSTV GND DIRECTN
MTA: 315° Lead
Range: 0 to 359 Lead in steps of 1
°
Enter the maximum torque angle by which the operating current leads the
polarizing voltage. This is the angle of maximum sensitivity. This setting affects
voltage polarizing only.
MINIMUM POLARIZING
VOLTAGE: 0.05 x VT
Range: 0.00 to 1.25 in steps of 0.01 x VT
This setting affects the voltage element only. As the system zero sequence
voltage is used as the polarizing voltage for this element, a minimum level of
voltage must be selected to prevent operation caused by system unbalanced
voltages or VT ratio errors. For well-balanced systems and 1% accuracy VTs,
this setpoint can be as low as 2% of VT nominal voltage. For systems with
high-resistance grounding or floating neutrals, this setpoint can be as high as
20%. The default value of
0.05 x VT
is appropriate for most solidly grounded
systems.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...