GE Power Management
750/760 Feeder Management Relay
16-
55
16 COMMUNICATIONS
16.4 MODBUS MEMORY MAP
16
1BB5
2
Lockout For Current Above
0.00 to 20.00
x CT
F3
20.00 x CT
S7
ZONE COORDINATION - 760 ONLY
READ/WRITE
1BB8
1
Zone Coordination Function
---
---
F30
Disabled
1BB9
1
Phase Current Increase
0.05 to 20.00
x CT
F3
1.00 x CT
1BBA
1
Neutral Current Increase
0.05 to 20.00
x CT
F3
1.00 x CT
1BBB
1
Maximum fault Clearing Time
1 to 1000
s
F1
10 s
S7
RECLOSURE SHOT 1 - 760 ONLY
READ/WRITE
1BC0
2
Deadtime Before Reclosure 1
0.00 to 300.00
s
F3
0.50 s
1BC1
1
Select Setpoint Group
---
---
F80
Active Group
1BC2
2
Overcurrent Blocking Flags
---
---
F59
None blocked
1BC3
1
Phase Time Overcurrent 1 Raised Pickup
0 to 100
%
F1
0%
1BC4
1
Neutral Time Overcurrent 1 Raised Pickup
0 to 100
%
F1
0%
1BC5
1
Ground Time Overcurrent Raised Pickup
0 to 100
%
F1
0%
1BC6
1
N ega tive S e que nce Tim e O vercu rre nt R aised P ickup
0 to 100
%
F1
0%
1BC7
3
Sensitive Ground Time Overcurrent Raised Pickup
0 to 100
%
F1
0%
S7
RECLOSURE SHOT 2 - 760 ONLY
READ/WRITE
1BD0
2
Deadtime Before Reclosure 2
0.00 to 300.00
s
F3
3.00 s
1BD1
1
Select Setpoint Group
---
---
F80
Active Group
1BD2
2
Overcurrent Blocking Flags
---
---
F59
None blocked
1BD3
1
Phase Time Overcurrent 1 Raised Pickup
0 to 100
%
F1
0%
1BD4
1
Neutral Time Overcurrent 1 Raised Pickup
0 to 100
%
F1
0%
1BD5
1
Ground Time Overcurrent Raised Pickup
0 to 100
%
F1
0%
1BD6
1
N ega tive S e que nce Tim e O vercu rre nt R aised P ickup
0 to 100
%
F1
0%
1BD7
3
Sensitive Ground Time Overcurrent Raised Pickup
0 to 100
%
F1
0%
S7
RECLOSURE SHOT 3 - 760 ONLY
READ/WRITE
1BE0
2
Deadtime Before Reclosure 3
0.00 to 300.00
s
F3
4.00 s
1BE1
1
Select Setpoint Group
---
---
F80
Active Group
1BE2
2
Overcurrent Blocking Flags
---
---
F59
None blocked
1BE3
1
Phase Time Overcurrent 1 Raised Pickup
0 to 100
%
F1
0%
1BE4
1
Neutral Time Overcurrent 1 Raised Pickup
0 to 100
%
F1
0%
1BE5
1
Ground Time Overcurrent Raised Pickup
0 to 100
%
F1
0%
1BE6
1
N ega tive S e que nce Tim e O vercu rre nt R aised P ickup
0 to 100
%
F1
0%
1BE7
3
Sensitive Ground Time Overcurrent Raised Pickup
0 to 100
%
F1
0%
Table 16–15: MODBUS MEMORY MAP (Sheet 38 of 41)
ADDR
DESCRIPTION
RANGE
UNITS
TYPE
FACTORY
DEFAULT
1 2 3 4 5 6 7 8 9
For explanation of Table footnotes, see page 16–59.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...