![GE 750 Скачать руководство пользователя страница 30](http://html.mh-extra.com/html/ge/750/750_instruction-manual_131794030.webp)
1-
14
750/760 Feeder Management Relay
GE Power Management
1.2 TECHNICAL SPECIFICATIONS
1 PRODUCT OVERVIEW
1
1.2.8 OUTPUTS
ANALOG OUTPUTS
Type: Active
Outputs:
8 Channels; specify one of the fol-
lowing output ranges when ordering:
Output Range Maximum Load
0-1 mA:
12 k
Ω
0-5 mA:
2.4 k
Ω
0-10 mA:
1.2 k
Ω
4-20 mA:
600
Ω
Isolation:
Fully isolated
Accuracy:
± 1% of full scale
Response Time:
100% indication in less than 6
power system cycles
(100 ms @ 60 Hz)
SOLID STATE TRIP
Make and Carry 15 A @ 250 V DC for 500 ms
OUTPUT RELAYS
Configuration:
1 TRIP: Form A
2 CLOSE: Form A
3-7 AUXILIARY: Form C
8 SELF-TEST WARNING: Form C
Contact Material:
silver alloy
Contact Ratings:
1 TRIP / 2 CLOSE:
Make:
30 A (per ANSI/IEEE C37.90)
Carry:
20 A continuous
Break:
DC 300 W resistive
DC 150 W inductive (L/R = 40 ms)
AC 5000 VA resistive
AC 5000 VA inductive (PF = 0.4)
3-7 AUXILIARY / 8 SELF-TEST WARNING
Make:
30 A (per ANSI/IEEE C37.90)
Carry:
5 A continuous
Break:
DC 150 W resistive
DC 90 W inductive (L/R = 40 ms)
AC 1250 VA resistive
AC 500 VA inductive (PF = 0.4)
Contact Durability:
100 000 operations (at 1800 opera-
tions/hour) at Rated Load
1.2.9 COMMUNICATIONS
ALL PORTS
300-19200 baud, programmable parity, Modbus RTU or
DNP 3.0 protocol
EEPROM
100000 program/erase cycles max.
1.2.10 CLOCK
Resolution:
1 ms
Accuracy with IRIG-B: ± 1 ms
Accuracy without
IRIG-B:
± 1 minute/month
Backup Battery Life:
10 years continuous use
1.2.11 PHYSICAL SPECIFICATIONS
ENVIRONMENT
Operating Temperature
Range:
–40 °C to +60 °C
Ambient Storage
Temperature:
–40 °C to +80 °C
Ambient Shipping
Temperature:
-40 °C to +80 °C
Humidity:
up to 90% noncondensing
Pollution Degree:
2
IP Rating:
40-X
CASE
Fully drawout unit (automatic CT shorts)
Meets CE drawout specifications
Seal provision
Dust tight door
Panel or 19" rack mount
Weight
(Case and Relay):
7.9 kg
Shipping Weight:
9.4 kg
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...