GE Power Management
750/760 Feeder Management Relay
5-
5
5 FRONT PANEL OPERATION
5.4 MESSAGES
5
5.4 MESSAGES
5.4.1 DIAGNOSTIC MESSAGES
Diagnostic messages are automatically displayed for any active conditions in the relay such as trips, alarms, or
asserted logic inputs. These messages provide a summary of the present state of the relay. The MESSAGE
indicator flashes when there are diagnostic messages available; press the
key to scroll through the
messages. The following shows the format of the various diagnostic messages.
5.4.2 SELF-TEST WARNINGS
The relay performs self diagnostics at initialization (after power-up), and continuously as a background task to
ensure that every testable unit of the hardware and software is alive and functioning correctly. There are two
types of self-test warnings indicating either a minor or major problem. Minor problems indicate a problem with
the relay that does not compromise protection of the power system. Major problems indicate a very serious
problem with the relay which comprises all aspects of relay operation.
SELF-TEST WARNINGS MAY INDICATE A SERIOUS PROBLEM WITH THE RELAY
HARDWARE!
Upon detection of either a minor or major problem, the relay will:
•
De-energize the 8 SELF-TEST WARNING relay.
•
Indicate the failure in the diagnostic message queue.
•
Record the failure in the EVENT RECORDER.
Upon detection of a major problem, the relay will (if possible) also:
•
Turn off the RELAY IN SERVICE indicator.
•
Inhibit operation of all output relays
.
PICKUP: <
Φ
>
< Cause >
These messages show any elements that are presently picked up.
TRIP: <
Φ
>
< Cause >
These messages indicate that an element has tripped. The message
remains in the diagnostic queue until the relay is reset.
ALARM: <
Φ
>
< Cause >
These messages show any elements that are presently operating and have
been programmed to have an alarm function. When an element is pro-
grammed to Latched Alarm, this message remains in the diagnostic queue
after the alarm condition clears until the relay is reset.
SELF-TEST WARNING:
< Cause >
These messages show any self-test warnings.
N E X T
WARNING
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...