9.4 POWER SYSTEM
9 S2 SYSTEM SETUP
9
9.4 POWER SYSTEM
9.4.1 SETTINGS
■
POWER SYSTEM
■
[ENTER] for more
The Power System setpoints path is:
\ SETPOINTS \ S2 SYSTEM SETUP \ POWER SYSTEM
NOMINAL FREQUENCY:
60 Hz
Range: 25 to 60 in steps of 1 Hz
Enter the nominal power system frequency. This value is used as a default to
set the optimal digital sampling rate if the system frequency cannot be mea-
sured as there is no voltage available at the bus voltage phase A input termi-
nals.
PHASE SEQUENCE
ABC
Range: ABC, ACB
Enter the phase sequence of the power system.
COST OF ENERGY:
5.0 ¢/kWh
Range: 1.0 to 25.0 in steps of 0.1 ¢/kWh
Kilowatt hour power usage is converted to a cost of energy using this setpoint.
The cost of energy charged by a utility is usually a variable rate depending on
total energy consumed or other factors. Enter an estimated average cost in
cents per kWh. Approximate energy cost will be determined by the relay, pro-
viding a value useful for budgeting purposes.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...