GE Power Management
750/760 Feeder Management Relay
10-
7
10 S3 LOGIC INPUTS
10.6 BLOCK FUNCTIONS
10
10.6 BLOCK FUNCTIONS
10.6.1 DESCRIPTION
The following logic input functions block various operations within the relay. Protection elements will NOT
detect faults, send messages, or illuminate indicators when blocked.
10.6.2 SETTINGS
■
BLOCK FUNCTIONS
■
[ENTER] for more
The Block Functions setpoints path is:
\ SETPOINTS \ S3 LOGIC INPUTS \ BLOCK FUNCTIONS
BLOCK 1 TRIP RELAY:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Blocks operation of the 1 TRIP relay. Protection features will still detect faults,
display messages, and illuminate indicators.
BLOCK 2 CLOSE RELAY:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
A system condition monitor such as ‘synchrocheck’ or ‘closing spring charged’
can be connected for close supervision. If this function is selected, this input
must be de-asserted to permit operation of the 2 CLOSE relay.
BLOCK RESET:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Blocks any attempted reset.
BLOCK UNDERVOLT 1:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Blocks the Undervoltage 1 element from operating. This input can be used
where automatic / manual modes are required.
BLOCK UNDERVOLT 2:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Blocks the Undervoltage 2 element from operating.
BLOCK UNDERVOLT 3:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Blocks the Undervoltage 3 element from operating.
BLOCK UNDERVOLT 4:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Blocks the Undervoltage 4 element from operating.
BLOCK UNDERFREQ 1:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Blocks the Underfrequency 1 element from operating.
BLOCK UNDERFREQ 2:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Blocks the Underfrequency 2 element from operating.
BLOCK FREQUENCY
DECAY: Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Blocks the Frequency Decay element from operating.
BYPASS SYNCHROCHECK:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Provides a manual override of the synchrocheck monitor, so an operator can
close the feeder breaker without the programmed synchrocheck condition.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...