10 S3 LOGIC INPUTS
10.8 TRANSFER FUNCTIONS
10
10.8 TRANSFER FUNCTIONS
10.8.1 DESCRIPTION
The following logic input functions are used exclusively for the bus transfer scheme. Refer to Section 14.7:
TRANSFER on page 14–18 for more detail.
If the bus transfer feature of the relay is required in an installation, all logic input functions necessary
for the operation of this scheme must be assigned to contact inputs before any other functions. This is
to ensure there are no conflicts.
10.8.2 SETTINGS
■
TRANSFER FUNCTIONS
■
[ENTER] for more
The Transfer Functions setpoints path is:
\ SETPOINTS \ S3 LOGIC INPUTS \ TRANSFER FUNCTIONS
SELECT TO TRIP:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Used to select the breaker to trip on prevent-parallel operation.
UNDERVOLT ON OTHER
SOURCE: Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Used for permission-to-transfer logic.
INCOMER 1 BREAKER
CLOSED: Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Used to track breaker state, for prevent-parallel or permission-to-transfer
logic.
INCOMER 2 BREAKER
CLOSED: Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Used to track breaker state, for prevent-parallel or permission-to-transfer
logic.
TIE BREAKER
CONNECTED: Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Used to inhibit transfers if the breaker cannot be used to pass current from the
source to the load, such as when it is in the Test or Disconnected positions.
TIE BREAKER
CLOSED: Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Used to track breaker state, for prevent-parallel or permission-to-transfer
logic.
BLOCK TRANSFER:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Used to disable the transfer scheme.
TRANSFORMER LOCKOUT:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Used to initiate a transfer as source 1 (2) is about to be lost.
SOURCE TRIP:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Used to initiate a transfer as source 1 (2) is about to be lost.
CLOSE FROM INCOMER1:
DECAY: Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Used to signal the bus tie breaker to begin a close operation.
CLOSE FROM INCOMER2:
DECAY: Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Used to signal the bus tie breaker to begin a close operation.
NOTE
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...