13.4 DEMAND
13 S6 MONITORING
13
13.4.2 CURRENT DEMAND
The current demand for each phase is calculated individually, and the demand for each phase is monitored by
comparing to a single current demand pickup value. If the current demand pickup is exceeded by any phase,
the relay can cause an alarm or signal an output relay.
■
CURRENT
■
[ENTER] for more
The
CURRENT
Demand setpoints path is:
\ SETPOINTS \ S6 MONITORING \ DEMAND \ CURRENT
CURRENT DEMAND
FUNCTION: Disabled
Range: Disabled, Alarm, Latched Alarm, Control
Selects the required function.
MEASUREMENT TYPE:
Thermal Exponential
Range: Thermal Exponential, Block Interval, Rolling Demand
Select one of three current demand calculation methods.
THERMAL 90% RESPONSE
TIME: 15 min
Range: 5 min, 10 min, 15 min, 20 min, 30 min, 60 min
This message is only displayed if the
MEASUREMENT TYPE
is selected as
Ther-
mal Exponential
. Enter the time required for a steady state current to indicate
90% of the actual value. This setpoint allows the user to approximately match
the response of the relay to analog instruments.
TIME INTERVAL:
20 min
Range: 5 min, 10 min, 15 min, 20 min, 30 min, 60 min
This message is only displayed if the
MEASUREMENT TYPE
is selected as
Block
Interval
or
Rolling Demand
. Enter the time period over which the current
demand calculation is to be performed.
CURRENT DEMAND
RELAYS (3-7):-----
Range: Any Combination of the 3-7 AUXILIARY Relays
Select the output relays required.
CURRENT DEMAND
PICKUP: 1000 A
Range: 10 to 10000 in steps of 1 A
Enter the threshold value for current demand. For example, if an action is
required when the current demand is above 1000 A, enter
1000
for this set-
point. When the maximum current demand in any phase exceeds this setting,
the programmed action will be performed.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...