GE Power Management
750/760 Feeder Management Relay
12-
7
12 S5 PROTECTION
12.2 DIRECTIONAL OVERCURRENT CHARACTERISTICS
12
12.2.2 PHASE OVERCURRENT
Phase overcurrent protection comprises two time overcurrent, two instantaneous overcurrent, and a phase
directional element. The directional element determines whether current flow is in the forward or reverse direc-
tion, as determined by the connected polarity of the input CTs and the Maximum Torque Angle selected for the
phase directional element. Each phase overcurrent element can be programmed to either disable directionality
or provide a trip for current flow in the forward/reverse direction only. Two elements allow the use of ‘Loset’ and
‘Hiset’ detectors in autoreclose applications, zone-selective (blocking) schemes, and distinct settings for faults
in different directions. Phase overcurrent protection elements can be blocked individually or by logic inputs.
12.2.3 PHASE TIME OVERCURRENT
Phase time overcurrent 1 and 2 are identical elements. Each consists of the equivalent of three separate time
overcurrent relays, ANSI device 51P, with identical characteristics. These elements can be controlled by the
phase directional element, providing operation for current flow in the permitted direction only. Voltage
restrained operation which reduces the pickup level with reduced voltage is also available.
■
PHASE TIME OC 1
■
[ENTER] for more
The Phase Time Overcurrent 1 setpoints path is:
\ SETPOINTS \ S5 PROTECTION \ PHASE CURRENT \ PHASE TIME OC 1
PHASE TIME OC 1
FUNCTION: Trip
Range: Disabled, Trip, Trip & AR, Alarm, Latched Alarm, Control
Select the required function.
PHASE TIME OC 1
RELAYS (3-7): -----
Range: Any Combination of the 3-7 AUXILIARY Relays
Select the output relays required.
PHASE TIME OC 1
PICKUP: 1.00 x CT
Range: 0.05 to 20.00 in steps of 0.01 x CT
Select the current level required.
PHASE TIME OC 1
CURVE: Ext Inverse
Range: Ext Inverse, Very Inverse, Norm Inverse, ..., FlexCurve B
See description in Section 12.1: TIME OVERCURRENT CURVE CHARAC-
TERISTICS on page 12–1.
PHASE TIME OC 1
MULTIPLIER:
1.00
Range: 0.00 to 100.00 in steps of 0.01
See description in Section 12.1: TIME OVERCURRENT CURVE CHARAC-
TERISTICS on page 12–1.
PHASE TIME OC 1
RESET: Instantaneous
Range: Instantaneous, Linear
See description in Section 12.1: TIME OVERCURRENT CURVE CHARAC-
TERISTICS on page 12–1.
PHASE TIME OC 1
DIRECTION: Disabled
Range: Disabled, Forward, Reverse
Select the direction(s) of current flow for which operation is permitted.
PHASE TIME OC 1 VOLT
RESTRAINT: Disabled
Range: Enabled, Disabled
Select
Disabled
for this setpoint if voltage restraint is not required. When set to
Enabled
, this feature lowers the pickup value of each individual phase time OC
element in a fixed relationship with the corresponding phase input voltage.
When voltage restraint is enabled, it is not allowed to change the pickup cur-
rent setting if the manual close blocking, cold load pickup blocking or autore-
close features are controlling the protection. If the
BUS INPUT VT TYPE
is
selected to
None
, this feature is automatically disabled.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...