GE Power Management
750/760 Feeder Management Relay
16-
9
16 COMMUNICATIONS
16.3 MODBUS PROTOCOL
16
Table 16–5: SUMMARY OF OPERATION CODES FOR FUNCTION 05H
OPERATION
CODE (HEX)
DEFINITION
DESCRIPTION
0000
NO OPERATION
Does not do anything.
0001
RESET
Performs the same function as the front panel
RESET
key.
0002
OPEN BREAKER
Performs the same function as the front panel
OPEN
key. The 760
must be in REMOTE mode for this operation to be effective.
0003
CLOSE BREAKER
Performs the same function as the front panel
CLOSE
key. The
760 must be in REMOTE mode for this operation to be effective.
0004
SET TIME
Sets the internal clock time. See 16.3.11 CLOCK
SYNCHRONIZATION OF MULTIPLE RELAYS on page 16–12.
0005
SET DATE
Sets the internal clock date. See 16.3.11 CLOCK
SYNCHRONIZATION OF MULTIPLE RELAYS on page 16–12.
0006
TRIGGER TRACE
MEMORY
Performs the same function as the logic input function
TRIGGER
TRACE MEMORY.
0007
CLEAR ENERGY
USE DATA
Performs the same function as front panel
CLEAR ENERGY USE
DATA
command.
0008
CLEAR MAX
DEMAND DATA
Performs the same function as the front panel
CLEAR MAX
DEMAND DATA
command.
0009
CLEAR EVENT
RECORDER DATA
Performs the same function as the front panel
CLEAR EVENT
RECORDER DATA
command.
000A
RESET TRIP
COUNTER DATA
Performs the same function as the front panel
RESET TRIP
COUNTER DATA
command.
000B
RESET ARCING
CURRENT DATA
Performs the same function as the front panel
RESET ARCING
CURRENT DATA
command.
000C
DISPLAY
OVERRIDE PACKET
Displays the 40 character (20 register)
Override_Packet
(memory
map addresses 10B1 to 10C4 hex) for the time specified in
Override_Time
(memory map address 10B0 hex).
000D
TRIGGER DATA
LOGGER
Performs the same function as the logic input function
TRIGGER
DATA LOGGER
.
000E
RESET TRACE
MEMORY
Resets the Trace Memory oscillography data by clearing the
number of captured events to zero.
000F
RESET DATA
LOGGER
Resets the Data Logger by clearing the number of captured events
to zero.
0010
RESET AR COUNT
DATA
Resets the Autoreclose Count by clearing the AUTORECLOSE
SHOT COUNT to zero.
0011
RESET AR RATE
DATA
Resets the Autoreclose Shot Rate by clearing the
AUTORECLOSE SHOT RATE to zero.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...