750/760 Feeder Management Relay
GE Power Management
14.4 COLD LOAD PICKUP BLOCKING
14 S7 CONTROL
14
PHASE INST OC 1
BLOCKING: Disabled
Range: Disabled, Enabled
Enter
Enabled
to block the Phase Instantaneous Overcurrent 1 element while
cold load pickup blocking is in effect.
NEUTRAL INST OC 1
BLOCKING: Disabled
Range: Disabled, Enabled
Enter
Enabled
to block the Neutral Instantaneous Overcurrent element while
cold load pickup blocking is in effect.
GROUND INST OC 1
BLOCKING: Disabled
Range: Disabled, Enabled
Enter
Enabled
to block the Ground Instantaneous Overcurrent element while
cold load pickup blocking is in effect.
SENSTV GND INST OC
BLOCKING: Disabled
Range: Disabled, Enabled
Enter
Enabled
to block the Sensitive Ground Instantaneous Overcurrent ele-
ment while cold load pickup blocking is in effect.
NEG SEQ INST OC
BLOCKING: Disabled
Range: Disabled, Enabled
Enter
Enabled
to block the Negative Sequence Instantaneous Overcurrent ele-
ment while cold load pickup blocking is in effect.
PHASE TIME OC 1
RAISED PICKUP:
0%
Range: 0 to 100 in steps of 1%
Selects the amount to raise the pickup level for the Phase Time Overcurrent 1
element while cold load pickup blocking is in effect.
NEUTRAL TIME OC 1
RAISED PICKUP:
0%
Range: 0 to 100 in steps of 1%
Selects the amount to raise the pickup level for the Neutral Time Overcurrent 1
element while cold load pickup blocking is in effect.
GROUND TIME OC
RAISED PICKUP:
0%
Range: 0 to 100 in steps of 1%
Selects the amount to raise the pickup level for the Ground Time Overcurrent
element while cold load pickup blocking is in effect.
SENSTV GND TIME OC
RAISED PICKUP:
0%
Range: 0 to 100 in steps of 1%
Selects the amount to raise the pickup level for the Sensitive Ground Time
Overcurrent element while cold load pickup blocking is in effect.
NEG SEQ TIME OC
RAISED PICKUP:
0%
Range: 0 to 100 in steps of 1%
Selects the amount to raise the pickup level for the Negative Sequence Time
Overcurrent element while cold load pickup blocking is in effect.
SELECT SETPOINT
GROUP: Active Group
Range: Group 1, Group 2, Group 3, Group 4, Active Group
S elect the setpoint group that w ill be used w hile cold load pickup blocking is in
effect. If
A ctive G roup
is selected then the active setpoint group is not affected.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...