16-
12
750/760 Feeder Management Relay
GE Power Management
16.3 MODBUS PROTOCOL
16 COMMUNICATIONS
16
16.3.11 CLOCK SYNCHRONIZATION OF MULTIPLE RELAYS
The time and date of multiple relays on the same communication link can be synchronized so that time stamp-
ing of events on different relays can be correlated. The following procedure describes how to synchronize the
clocks of multiple relays. Since the clock is accurate to 1 minute per month, performing this procedure every 10
minutes will result in synchronization accuracy of ±10 ms.
1.
Store values for the date and time setpoints Set Date and Set Time at locations 1006h and 1008h in the
Memory Map respectively into each slave device.
2.
Broadcast (via slave address 0) the SET DATE operation code via function code 05h to all connected
slaves to synchronize the dates.
3.
Broadcast (via slave address 0) the SET TIME operation code via function code 05h to all connected
slaves to synchronize the times. If synchronizing to an external clock source then this command should be
sent when the time is equal to the value stored in SET TIME.
The following table shows the format of the master and slave packets for a master device storing the date of
June 10, 1994 and time of 2:15:30 PM to slave device 11 as required by step one of the procedure.
Table 16–10: MASTER/SLAVE PACKET FORMAT FOR CLOCK SYNCHRONIZATION
MASTER TRANSMISSION
SLAVE RESPONSE
PACKET FORMAT
EXAMPLE (HEX)
PACKET FORMAT
EXAMPLE (HEX)
SLAVE ADDRESS
11
SLAVE ADDRESS
11
FUNCTION
CODE 10
FUNCTION
CODE 10
DATA STARTING ADDRESS - hi
10
DATA STARTING ADDRESS - hi
10
DATA STARTING ADDRESS - lo
06
DATA STARTING ADDRESS - lo
06
NUMBER OF SETPOINTS - hi
00
NUMBER OF SETPOINTS - hi
00
NUMBER OF SETPOINTS - lo
04
NUMBER OF SETPOINTS - lo
08
BYTE COUNT
08
CRC - lo
27
DATA #1 - hi (Month = 6)
06
CRC - hi
9B
DATA #1 - lo (Day = 10)
0A
DATA #2 - hi (Year=1994=07CAh)
07
DATA #2 - lo (Year=1994=07CAh)
CA
DATA #3 - hi (Hour=2pm=14)
0E
DATA #3 - lo (Minute=15)
0F
DATA #4 - hi (Sec=30000ms=7530h)
75
DATA #4 - lo (Sec=30000ms=7530h)
30
CRC - lo
37
CRC - hi
0C
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...