1 / 2
HRF-10
cos φ ≥ 0.95
M
M
HAL.230V
K
M
M
AC12
250V / 1A
DC14
x
AC1
250V / 8A
AC13
x
AC2
250V / 3A
AC14
250V / 3A
AC3
250V / 2A
AC15
250V / 3A
AC5b
300W
DC5
24V / 2A
AC6a
x
DC12
24V / 8A
AC7b
250V / 1A
DC13
24V / 2A
02-15/2017 Rev.: 0
1
6
7
8
5
2
3
9
10
4
16 15 18 28 25 26
N L
L
N
DC1
24V / 8A
DC3
24V / 3A
Made in Czech Republic
ELKO EP, s.r.o.
Palackého 493
769 01 Holešov, Všetuly
Czech Republic
Tel.: +420 573 514 211
e-mail: [email protected]
www.elkoep.com
Frequency monitoring relay
•
the relay serves to monitor frequency of AC voltage, e.g. in photovoltaic power
stations, generators
•
the monitored frequency 50 / 60 / 400 Hz is selected by a switch
•
supplied from monitored voltage
•
two adjustable levels of frequency (Fmin, Fmax) in the range of 80 - 120 % Fn
•
adjustable diff erence level
•
adjustable delay level
•
switchable ranges of rated frequency Fn
•
3-MODULE design, DIN rail mounting
Characteristics
Description
Connection
Type of load
Mat. contacts AgNi,
contact 8A
Type of load
Mat. contacts AgNi,
contact 8A
AC5a
uncompensated
230V/1.5A (345VA)
AC5a
compensated
x
EN
1. Supply voltage indication
2. Indication F > Fmax
3. Indication F < Fmin
4. Output contact
5. Supply / monitored voltage terminals
6. Delay setting
7. Diff erence setting
8. Fmax setting
9. Fn setting
10. Fmin setting