HRF-10

Fmax

Fmin

25-28

15-18

OVER LED

UNDER LED

 LED

t

t

t

Warning

Technical parameters

Device is constructed for connection in 1-phase main alternating current voltage and 
must be installed according to norms valid in the state of application. Connection 
according to the details in this direction. Installation, connection, setting and servicing 
should be installed by qualifi ed electrician staff  only, who has learnt these instruction 
and functions of the device. This device contains protection against overvoltage 
peaks and disturbancies in supply. For correct function of the protection of this device 
there must be suitable protections of higher degree (A, B, C) installed in front of them. 
According to standards elimination of disturbancies must be ensured. Before installation 
the main switch must be in position “OFF” and the device should be de-energized. 
Don´t install the device to sources of excessive electro-magnetic interference. By correct 
installation ensure ideal air circulation so in case of permanent operation and higher 
ambient temperature the maximal operating temperature of the device is not exceeded. 
For installation and setting use screw-driver cca 2 mm. The device is fully-electronic - 
installation should be carried out according to this fact. Non-problematic function 
depends also on the way of transportation, storing and handling. In case of any signs 
of destruction, deformation, nonfunction or missing part, don´t install and claim at your 
seller.

Function

Supply and monitoring terminals:

Supply voltage:

Rated frequency Fn:

Burden (max):

Overload capacity

- continuous:

- max. 10 s:

Frequency Fmax:

Frequency Fmin:

Diff erence:

Delay (until failure):

Opening level (Uopen):

Output relay - contact:

AC contact capacity:

DC contact capacity:

Mechanical life:

Other information

Operating temperature:

Storage temperature:

Electrical strenght

(supply - relay contact):

Protection degree:

Pollution degree:

Protection degree:

Max. cable size (mm

2

):

Dimensions:

Weight:

Standards:

L, N

161 - 346 V

50 / 60 / 400 Hz

1.7 VA / 1.1 W

346 V

416 V

adjustable 80 - 120 % Fn

adjustable 80 - 120 % Fn

adjustable 0.5 - 5 % Fn

adjustable 0.5 - 10 s

161 V

2x changeover / SPDT (AgNi) gilded

250 V / 8 A, max. 2000 VA

30 V / 8 A

3x10

6

 at rated load

-20 °C to 55 °C (-4 °F to 131 °F)

-30 °C to 70 °C (-22 °F to 158 °F)

4 kV / 1 min.

III.

2

IP40 from font panel / IP20 terminals

max. 2x 1.5 / 1x 2.5 (AWG 12)

90 x 52 x 64 mm (3.5 x 2 x 2.6˝)

125 g (4.4 oz.)

EN 60255-6, EN 60255-27, EN 61000-6-2, EN 61000-6-4

After the supply (monitored) voltage is connected, the green LED is on.
If the value of the monitored frequency falls within the range between the two set levels 
Fmin - Fmax no red LED is on. The relay UNDER is triggered (contacts 15-16-18) and the 
relay OVER is disconnected (contacts 25-26-28).
If the monitored frequency exceeds the set level Fmax, the relay OVER is triggered after 
the set delay timing elapses and the red LED OVER goes on. The red LED fl ashes during 
the timing.
If the monitored frequency drops below Fmax - diff erence, the relay is activated without 
delay and the red LED OVER goes off .
If the monitored frequency drops below the set level Fmin, the relay UNDER is 
disconnected after the set delay timing elapses and the red LED UNDER goes on. The red 
LED fl ashes during the timing. If the monitored frequency exceeds the level Fmin + the 
diff erence, the relay is triggered without delay and the red LED UNDER goes off .
If the monitored voltage is lower than the opening level Uopen both the relays are 
disconnected and both the red LED (UNDER and OVER) start fl ashing slowly - indicating 
insuffi

  cient supply voltage.

diff erence

diff erence