background image

 
 

    

 
Type EB3N Relay Barrier

 

Associated Apparatus providing Intrinsically safe outputs   

for use in the following hazardous(classified) locations. 

Class

, Zone 0, [AExia]IIC 

Class

,

,

, Div. 1.GrpsA,B,C,D,E,F and G 

 
When installing an IDEC Type EB3N Relay Barrier, make sure it conforms to the following drawings and descriptions 

as well as all applicable requirements.

 

ANSI/NFPA70. 

 

This associated apparatus may also be connected to simple apparatus as defined in Article 504.2 and 
installed and temperature classified in accordance with Article 504.10(B) of the National Electrical Code 

(ANSI/NFPA 70), or other local codes, as applicable. 

Capacitance and inductance of the field wiring from the intrinsically safe equipment to the associated 

apparatus shall be calculated and must be included in the system calculations as shown in Note 2 of Table 2 

below. Cable capacitance, Ccable, plus intrinsically safe equipment capacitance, Ci must be less than the 

marked capacitance, Ca (or Co), shown on any associated apparatus used.   The same applies for inductance 

(Lcable, Li and La or Lo, respectively). Where the cable capacitance and inductance per foot are not known, 

the following values shall be used: Ccable = 60 pF/ft., Lcable = 0.2 µH/ft. 

Associated apparatus must be installed in an enclosure suitable for the application in accordance with the 

National Electrical Code (ANSI/NFPA 70) for installation in the United States, the Canadian Electrical 

Code for installations in Canada, or other local codes, as applicable. 

Where multiple circuits extend from the same piece of associated apparatus, they must be installed in 

separate cables or in one cable having suitable insulation.   Refer to Article 504.30(B) of the National 

Electrical Code (ANSI/NFPA 70) and Instrument Society of America Recommended Practice ISA RP12.6 for 

installing intrinsically safe equipment.   

Intrinsically safe circuits must be wired and separated in accordance with Article 504.20 of the National 

Electrical Code (ANSI/NFPA 70) or other local codes, as applicable. 

This associated apparatus has not been evaluated for use in combination with another associated 

apparatus. 

Control equipment must not use or generate more than 120 V rms or dc with respect to earth.   

For installations in which both the Ci and Li of the intrinsically safe apparatus exceeds 1% of the Co and Lo 

parameters of the associated apparatus (excluding the cable), then 50% of Co and Lo parameters are 

applicable and shall not be exceeded. 

 

・・

Servicing  –  Replacement  and  Repairs

: : 

Inspection and replacement of the Relay Barriers shall not be made until 

power is disconnected and shall not be connected again until all replacement Relay Barriers are properly re-assembled. 

All electrical components, including the interconnecting wiring, shall be kept in safe condition. Defective Relay Barriers 

should be returned to the factory for repair.   

WARNING : Substitution of components or unauthorized repair may impair intrinsic safety of apparatus. 
AVERTISSEMENT : La substitution de composants peut compromettre la sécurité intrinsèque de l’appareil. 

・・

Mounting

 : 

All bolts, nuts, screws, and other means of fastening, including the unused wiring screws, shall be   

fastened in place, properly tightened and secured. Mount the Relay Barrier on a 35mm track or directly mount on a 

panel surface using screws. 

 

・・

Certified Relay Barrier

Type EB3N

-abc   “

EB3N

”= Series type  

a = 

Safety circuit   

    

A2 

for auto start, 2 I/O

        

M2

 :

 

for manual start, 2 I/O

 

b = 

Auxiliary circuit    

N  

: without auxiliary circuit,   

R5 

:, relay output, 5 I/O 

c = 

Power supply 

     

D

  : 

24V DC 

 

・・

Table 1:Operations

  

 
 
 
 
 
 
 
 
 
 
 

IDEC CORPORATION 
6-64, Nishi-Miyahara, 2-Chome, Yodogawa-Ku,   
Osaka 532-0004, Japan          www.idec.com

 

Installation Manual

 

 

Terminals 

Ratings 

Power Supply 

Input:  + , - 

24V DC (-15%,+10%)

 

Class 2 

Input:  11-12, 21-22 

12V DC, 10 mA (source) 

Safe Circuit 

Output  13-14, 23-24 

2NO: DC-13  24V, 1A(Ind.) 

30V DC, 1A(Res.) 

Input:  P-N 

12V DC, 10mA (source) 

Auxiliary Circuit 

Output  A-C 

5NO/common: 24V DC, 3A(Res.) 

Reset Circuit 

Input:  Y1-Y2 

24V DC, 5 mA 

 

Draw. No. B-1156-4

   

Rev. B, Oct. 15, 2014 

Содержание EB3N

Страница 1: ...t be wired and separated in accordance with Article 504 20 of the National Electrical Code ANSI NFPA 70 or other local codes as applicable This associated apparatus has not been evaluated for use in combination with another associated apparatus Control equipment must not use or generate more than 120 V rms or dc with respect to earth For installations in which both the Ci and Li of the intrinsical...

Страница 2: ...2 EB3N 2 5 D 4 8 0 227 2 EB3N 2 D 1 7 EB3N 2 5 D 1 4 5 184 6 EB3N 2 D 2 8 EB3N 2 5 D 1 6 4 227 2 EB3N 2 D 3 EB3N 2 5 D 1 8 0 227 2 EB3N 2 D 1 EB3N 2 5 D 2 6 4 227 2 EB3N 2 D 1 EB3N 2 5 D 3 8 0 227 2 since these are included in the other connection number circuit actual wiring does not need Io mA 14 2 28 4 42 6 56 8 71 0 85 2 99 4 113 6 127 8 142 0 156 2 170 4 184 6 198 8 213 0 227 2 Po mW 46 9 93 ...

Страница 3: ...on classified Uo 13 2V Io 113 6mA Po 375 9mW Lo Co Refer to Table2 Uo 13 2V Io 170 4mA Po 562 4mW Lo Co Refer to Table2 11 12 N1 21 22 N2 Y1 Y2 13 14 23 24 EB3N 2 D Power supply and General circuit Instrically Safe Circuit Instrically Safe Apparatus 11 12 N1 21 22 N2 Y1 Y2 13 14 23 24 EB3N 2 D Instrically Safe Circuit 11 12 N1 21 22 N2 Y1 Y2 13 14 23 24 EB3N 2 D Instrically Safe Circuit 11 12 N1 2...

Страница 4: ...fe Location classified Non classified Haz Location Safe Location classified Non classified Haz Location Safe Location classified Non classified Uo 13 2V Io 227 2mA Po 750mW Lo Co Refer to Table2 Uo 13 2V Io 184 6mA Po 609 2mW Lo Co Refer to Table2 Uo 13 2V Io 227 2mA Po 750mW Lo Co Refer to Table2 ...

Отзывы: