14 S7 CONTROL
14.8 AUTORECLOSE (760 ONLY)
14
14.8.4 AUTORECLOSE CURRENT SUPERVISION
The current supervision feature is used to limit breaker wear. When fault current exceeds user-programmed
levels, it reduces the number of reclose shots permitted.
Once a reclose sequence is initiated, the maximum current measured on any phase is compared to the set-
point current levels. The relay then determines the maximum number of shots allowed or whether the scheme
goes immediately to lockout. The lowest number of permitted shots, whether set by the
MAXIMUM NUMBER OF
RECLOSE SHOTS
setpoint or the current supervision feature, always takes precedence unless current supervi-
sion takes the scheme to lockout. Lockout has the highest priority. Once the current supervision feature has
reduced the total number of shots, a subsequent shot can still reduce the limit further.
■
CURRENT SUPERVSION
■
[ENTER] for more
The Autoreclose Current Supervision setpoints path is:
\ SETPOINTS \ S7 CONTROL \ AUTORECLOSE \ CURRENT SUPERVSION
CURRENT SUPERVISION
FUNCTION: Disabled
Range: Enabled, Disabled
Enables or disables the autoreclose current supervision scheme.
3 SHOTS FOR CURRENT
ABOVE: 17.00 x CT
Range: 0.00 to 20.00 in steps of 0.01 x CT
Selects the fault current level above which the number of autoreclose shots
will be reduced to three.
2 SHOTS FOR CURRENT
ABOVE: 18.00 x CT
Range: 0.00 to 20.00 in steps of 0.01 x CT
Selects the fault current level above which the number of autoreclose shots
will be reduced to two.
1 SHOT FOR CURRENT
ABOVE: 19.00 x CT
Range: 0.00 to 20.00 in steps of 0.01 x CT
Selects the fault current level above which the number of autoreclose shots
will be reduced to one.
CURRENT SUPERVISION
TO LOCKOUT: Disabled
Range: Enabled, Disabled
If the autoreclose scheme is to be taken directly to lockout without reclosing,
set this setpoint to Enabled.
LOCKOUT FOR CURRENT
ABOVE: 20.00 x CT
Range: 0.00 to 20.00 in steps of 0.01 x CT
Selects the fault current level above which the autoreclose scheme will go to
lockout.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...